en | Planning
HCP 0006 A, Fully Configured Panel, with Installation Sequence
BCM-0000-B
Figure 3.6: Example of configuration with HCP 0006 A Modular Panel Housing for 6 Modules
3.8

Configuration of BCM Battery Controller Module

The panel can be powered by up to 8 BCM-0000-B Battery Controller Modules, each with its
own UPS 2416 A Universal Power Supply. Current consumption is equally distributed among
all battery controller modules.
Notes
09.2017 | 11.3 | F.01U.028.089
10
2
PRS-0002-C
PRD 0004 A
11
<= 4 Module
FPO-5000-PSB-CH
1
9
UPS 2416 A
The 24 V switch outputs may not be connected in parallel.
The total current for all connected components including the battery charge current may
not exceed 6 A.
MPC
6
3
System Information
Modular Fire Panel
ADC xxxxx A
5
RLU 0000 A
HCP 0006 A
7
8
12 V / 28 Ah
12 V / 28 Ah
Bosch Sicherheitssysteme GmbH