108 en | Installation
Notice!
The requirements of the local fire department must be taken into account during
programming.
The module is used almost exclusively in Germany.
Figure 4.59: ENO 0000 B Fire Service Interface Module
Labeling
A
B
C
ÜE
NQuit
GND
ÜE+ | ÜE-
1
2
5
8
6 | 7
9
10
FSE+ | −
⊗ + | −
Information on the redundant connection of the module can be found in Redundancy, page 40.
09.2017 | 11.3 | F.01U.028.089
Transmission device to the fire brigade
Key deposit
Signal lamp (e.g. BEGA flush-mounting lamp or BL 200)
FSE release element monitoring
Four freely programmable changeover relays
Connection
Ground
Transmission unit control
Feedback contact
Automatic dialer and transmission unit fault
Acknowledge
Ground
Power supply of transmission unit
Monitoring key deposit
Ground
Door release magnet, +12 V/24 V, approx. 10 W
Key deposit lock monitoring
Ground
Heating, +24 V, approx. 8 W
Ground
FSE release element monitoring
Signal lamp, e.g. BEGA lamp +24 V, approx. 10 W
Relay 1-4