152 en | Technical Data
Installation of the power supply unit is described in CZM 0004 A 4 Zone Conventional Module,
page 107.
7.5.4
ENO 0000 B Fire Service Interface Module
Operating and display elements
Input voltage
Current consumption
In standby
All relays tripped
Key deposit heating
Permissible relay contact load
Space required (H x W x D)
Weight
Installation of the power supply unit is described in ENO 0000 B Fire Service Interface Module,
page 107.
7.5.5
FPE‑5000‑UGM Interface Module
Operating and display elements
Input voltage
Maximum cable length
Maximum line resistance
Transmission rate
Maximum current consumption
Space required (H x W x D)
Weight
Installation of the power supply unit is described in FPE‑5000‑UGM Interface Module, page 109.
7.5.6
IOP 0008 A Input/Output Module
Input voltage
Maximum current consumption
Maximum switch-on current
Maximum cable length
Space required (H x W x D)
09.2017 | 11.3 | F.01U.028.089
2 LEDs (1 x red, 1 x yellow)/1 button (LED
test)
20 V DC to 30 V DC
25 mA
60 mA
additional 240 mA
1 A/30 V
approx. 127 x 96 x 60 mm
approx. 150 g
Standby operation
One transmission path active
Both transmission paths active
4 two color LEDs (green = transmission / yellow
= fault), 1 button (LED test)
20 V DC to 30 V DC/5 V DC ± 5 %
1000 m
70 Ω
9600 bit/s at 1000 m to 38400 bit/s at 200 m
7 mA (at 24 V)
10 mA (at 24 V)
13 mA (at 24 V)
approx. 110 x 90 x 60 mm
approx. 150 g
20 V DC to 30 V DC/5 V DC ± 5 %
15 mA at 24 V DC
700 mA (short-circuit protected, I
3 m
approx. 127 x 96 x 60 mm
System Information
Modular Fire Panel
= 1.5 A)
max
Bosch Sicherheitssysteme GmbH