Chapter 11 Description of Parameter SettingsAFE2000 Series
Settings
This parameter is the response delay time after AFE unit receives communication command as
shown in the following.
RS-485 BUS
PC or PLC command
COM2Transmission Speed
Settings
This parameter is used to set the transmission speed between the RS485 master (PLC, PC, etc.) and
AFE2000 unit.
COM2 Transmission Fault Treatment
Settings
This parameter is set to how to react if transmission errors occur.
COM2 Time-out Detection
Settings
It is used to set the transmission time between communication and keypad.
COM2 Communication Protocol
Settings
0.0~200.0ms
Handling time
of the AFE unit
4.8~115.2kbits/s
0: Warning and continue to operate
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue to operate
0.0~100.0sec
0.0: No detection
0:7,N,1 for ASCII
1:7,N,2 for ASCII
2:7,E,1 for ASCII
3:7,O,1 for ASCII
4:7,E,2 for ASCII
5:7,O,2 for ASCII
6:8,N,1 for ASCII
7:8,N,2 for ASCII
8:8,E,1 for ASCII
9:8,O,1 for ASCII
10:8,E,2 for ASCII
11:8,O,2 for ASCII
11-94
Response Message
of the AFE unit
Response Delay Time
Factory Setting: 19.2
Factory Setting: 3
Factory Setting: 0.0
Factory Setting: 13