Chapter 11 Description of Parameter SettingsAFE2000 Series
Digital Input Response Time
Settings
It is used for digital input terminal signal delay and confirmation. The delay time is the confirmation
time to prevent some uncertain interference that would cause error in the digital input terminals
(M1~8). Under this condition, confirmation for this parameter would improve effectively, but the
response time will be somewhat delayed.
Digital Input Operation Direction
Settings 0~65535
This function is for bit setting. Bit =1 indicate the multi-function output is in a reverse direction. For
example: Pr.02-08 =1 (operating), when forward direction ouput bit is set to 0, Relay 1 will be ON
when the drive is operating and Relay 1 will be OFF when the drive stops. Conversely, if reverse
direction output bit is set to 1, Relay 1 will be OFF when the drive is operating and Relay 1 will be
ON when the drive stops.
Multi-Function Output(Relay1)
Multi-Function Output(Relay2)
Multi-Function Output(MO1)
Multi-Function Output(MO2)
0: Disable
1: Operation indication
2: DCBUS command attained
3: AFE Ready (Phase lock complete)
4: Fault Indication
5: Overheat warning (Pr.03-05 & Pr.03-06)
6: Output warning
7: Drive / Regenerate
8: Fault Reset
 This parameter is user defined setting to select the functions for each multi-function terminal.
Summary of function settings:
Settings
0
Disable
Operation indication
1
DCBUS command attained
2
AFE Ready (Phase lock
3
complete)
Fault Indication
4
Overheat warning
(03-05&03-06)
5
6
Output warning
0.001~30.000sec
Functions
Output terminal is disabled
When AFE2000 is at operation status, the contact is closed
(NC).
When DC Bus voltage level is attained, the contact is closed
(NC).
When there's no fault occurs in AFE2000 and phase lock is
complete, the contact is closed (NC).
When the drive detects unusual faults, the contact is closed
(NC).
When IGBT temperature or the ambient temperature is
greater than Pr.03-05, it will release a warning before
overheat causes AFE2000 shut down.
When AFE2000 detects a warning, the contact is closed
Descriptions
11-80
Factory Setting: 0.005
Factory Setting: 0
Factory Setting: 2
Factory Setting: 3
Factory Setting: 0
Factory Setting: 0