Delta Electronics AFE075A43A User Manual page 17

Afe2000 series. active front end unit
Table of Contents

Advertisement

Frame C
+
DC-
DC+
r1/l1
s1/l2
t1/l3
R/L1
S/L2
T/L3
DETECTION
POWER
Main circuit terminals:
R(L1), S(L2), T(L3),
Max. Wire
Models
AFE150A23A
1/0 AWG
AFE220A23A
(53.5mm
AFE220A43A
UL installations must use 600V, 75℃ or 90℃ wire. Use copper wire
only.
DC+ & DC-: must use 1kV Wire.
NOTE
Wire Gauge
Terminal r1/l1, s1/l2,
t1/l3:
Torque: 12 kg-cm [10.4 lb-in.] (1.18Nm) (±10%)
When surrounding temperature exceeds 45℃, please use 600V,90℃ wire for
model AFE220A23A.
If additional terminal is needed when wiring, please refer to Figure 1 for
additional terminal dimension.
After crimping the wire to the ring lug please apply the UL approved R/C
(YDPU2) heat shrink tubing rate min 600Vac to the terminal. The insulation shall
be all over the live part. Please refer to Figure 2.
Detection wire
Figure 1
Power wire
Figure 1
4-15
Chapter 4 Main Circuit TerminalsAFE2000 Series
, DC+, DC-
Min. Wire Gauge
Gauge
1 AWG (42.4mm
1/0 AWG (53.5mm
2
)
4 AWG (21.2mm
:20AWG [0.5mm²] ~ 14 AWG [2.1mm²]
Torque
(±10%)
2
)
M8
2
80kg-cm
)
(69.4 lb-in.)
2
)
(7.85Nm)
Figure 2
Figure 2

Hide quick links:

Advertisement

Table of Contents
loading