Advertisement

Content
4. Exception response:
The AC motor drive is expected to return a normal response after receiving command messages
from the master device. The following depicts the conditions when no normal response is replied to
the master device.
The AC motor drive does not receive the messages due to a communication error; thus, the AC
motor drive has no response. The master device will eventually process a timeout condition.
The AC motor drive receives the messages without a communication error, but cannot handle them.
An exception response will be returned to the master device and an error message "CExx" will be
displayed on the keypad of AC motor drive. The xx of "CExx" is a decimal code equal to the
exception code that is described below.
In the exception response, the most significant bit of the original command code is set to 1, and an
exception code which explains the condition that caused the exception is returned.
Example:
STX
Address
Function
Exception code
LRC CHK
END
The explanation of exception codes:
Exception code
1
2
3
4
10
Response Delay Time
Chapter 11 Description of Parameter SettingsAFE2000 Series
Address
2105H
DC-BUS Voltage (UXXX.X)
220EH
Display the IGBT temperature of AFE200 power module in
220FH
Display the ambient temperature in
2210H Analog input status ON/OFF
2211H Analog output status ON/OFF
2213H The corresponding CPU pin status of digital input
2214H The corresponding CPU pin status of digital output
ASCII mode:
':'
'0'
'1'
'8'
'6'
'0'
'2'
'7'
'7'
CR
LF
Illegal data value:
The data value received in the command message is not available for the
AFE unit.
Illegal data address:
The data address received in the command message is not available for
the AC motor drive.
Parameters are locked: parameters can't be changed
Parameters can't be changed during operation
Communication time-out.
Function
Address
Function
Exception code
CRC CHK Low
CRC CHK High
Explanation
11-93
o
C
RTU mode:
01H
86H
02H
C3H
A1H
Factory Setting: 2.0
o
C