Chapter 13 Fault Codes and Descriptions AFE2000 Series
Fault Name
Fault
DC BUS voltage is less than
LvS
Pr.03-00 at stop
Lv at stop
IGBT overheating
IGBT temperature exceeds
Fault
protection level
oH1
1~50HP: 105 ; 60~100HP:
IGBT over heat
110℃
Heatsink overheating
Fault
Capacitance temperature exceeds
oH2
protection level.
1~50HP: 80 ; 60~100HP: 65
Heat Sink oH
Fault
IGBT Hardware Error
tH1o
Thermo 1 open
Fault
Capacitor Hardware Error
tH2o
Thermo 2 open
Overload
Fault
The AC motor drive detects
oL
excessive drive output current.
Over load
Internal EEPROM can
Fault
not be programmed or
cF1
Internal EEPROM can
not be read.
EEPROM write err
Fault
Internal EEPROM can not be
cF2
read.
EEPROM read err
Fault Descriptions
13-104
Corrective Actions
1.
Check if the input voltage is normal
2.
Check for possible sudden load
1.
Ensure that the ambient temperature
falls within the specified temperature
range.
2.
Make sure that the ventilation holes are
not obstructed.
3.
Remove any foreign objects from the
heatsinks and check for possible dirty
heat sink fins.
4.
Check the fan and clean it.
5.
Provide enough spacing for adequate
ventilation.
1.
Ensure that the ambient temperature
falls within the specified temperature
range.
2.
Make sure heat sink is not obstructed.
Check if the fan is operating
3.
Check if there is enough ventilation
clearance for AC motor drive.
Return to the factory
Return to the factory
1.
Increase AFE2000 output capacity.
Replace with the next higher power
AFE2000 unit.
1. Press "RESET" key to the factory setting
2. Return to the factory.
1. Press "RESET" key to the factory setting
2. Return to the factory.