Chapter 11 Description of Parameter SettingsAFE2000 Series
03 Protection Parameters
Low Voltage Level
Settings 230V model:160.0~220.0V
 This parameter is used to set the Low Voltage Level.
Current Limit (Drive)
Settings 0~250%
This parameter sets the maximum current limit for AFE2000 at drive status.
Current Limit (Regenerate)
Settings 0~250%
This parameter sets the maximum current limit for AFE2000 at energy regenerating status.
Phase Lock Frequency Deviation Level
Settings 0.00~10.00Hz
When AFE2000 detects phase lock frequency attain 47~63Hz and fluctuate within 1Hz for longer
than 300 ms, AFE2000 phase lock is completed.
Phase Lock Frequency Deviation Time
Settings 0~1000ms
 If the frequency detected is greater than the phaselock frequency and greater than the setting in
Pr.03-03 for a time period longer than Pr.03-04, it will output a phase lock errorsignal (PLE).
IGBT Temperature Warning Level
Settings 0.0~11.0℃
460Vmodel: 320.0~440.0V
input voltage
Pr. 06-00
 This parameter can be set during the operation.
30V(60V)
LV
11-82
Factory
Setting:
180.0/360.0
Factory Setting: 150
Factory Setting: 150
Factory
Setting:
4.00
Factory Setting: 150
Factory
Setting:
100.0