Advertisement

Fault Name
Fault
R-phase error
cd1
Ias sensor err
Fault
S-phase error
cd2
T-phase error
Ibs sensor err
Fault
W-phase error
cd3
Ics sensor err
Fault
cc (current clamp)
Hd0
cc HW error
Fault
oc hardware error
Hd1
Oc HW error
Fault
ov hardware error
Hd2
Ov HW error
Fault
occ hardware error
Hd3
occ HW error
Fault
External fault
EF
External fault
Fault
Emergency stop
EF1
Emergency stop
Fault
Wrong password input
Pcod
(3 times)
Password error
Chapter 13 Fault Codes and Descriptions AFE2000 Series
Fault Descriptions
13-105
Corrective Actions
Reboots the power. If fault code is still appears
on the keypad please return to the factory
Reboots the power. If fault code is still appears
on the keypad please return to the factory
Reboots the power. If fault code is still appears
on the keypad please return to the factory
Reboots the power. If fault code is still appears
on the keypad please return to the factory
Reboots the power. If fault code is still appears
on the keypad please return to the factory
Reboots the power. If fault code is still
displayed on the keypad please return to the
factory
Reboots the power. If fault code is still
displayed on the keypad please return to the
factory
1. When EF (N.O.) external terminal is ON.
AC motor drive stop output.
2. Press RESET after fault has been
cleared.
1. When the multi-function input terminals
MI1 to MI6 are set to emergency stop,
the AC motor drive stops output.
2. Press RESET after fault has been
cleared.
1. Refer to Pr.00-07 and 00-08.
2. Turn off the power then turn it on again
and enter the correct password.