Chapter 10 Summary of Parameter SettingsAFE2000 Series
03 Special Protection Parameters
Parameter
Explanation
03-00
Low Voltage Level
03-01
Current Limit (Drive)
03-02
Current Limit (Regeneration )
03-03
Phase Lock Frequency
Deviation Level
03-04
Phase Lock Frequency
Deviation Time
03-05
IGBT Temperature Warning
Level
03-06
Ambient Temperature
Warning Level
03-07
Numbers of Fault Retry
03-08
Fault Retry Reset Time
03-09
Fan Control
(only ON/OFF for Frame B)
03-10
Voltage Boosting Error (Level
Setting)
03-11
Voltage Boosting Error (Time
Setting)
03-12
Work Delete
03-13
Electricity cost
Settings
230V model: 160.0~220.0Vdc
460V model: 320.0~440.0Vdc
0~250%
0~250%
0.00~10.00Hz
0~1000ms
0.0~110.0 ℃
0.0~110.0 ℃
0~10
1~600 sec
0: Fan is always ON
1: As the drive stops, the fan will continue to run for
60 sec then stop.
2: Fan stops when the drive stops operation
3: Fan ON/OFF depends on the ambient
temperature
4: Fan is always OFF
0.0V ~15.0V
200ms~1000ms
1:
Delete (when deleting is completed, Pr.03-12
reset to 1)
0~6553.5
10-68
Factory
Setting
180
360
150
150
4.00
150
100.0
60.0
0
600
2
5.0
200
0
3.0