Delta Electronics AFE075A43A User Manual page 18

Afe2000 series. active front end unit
Table of Contents

Advertisement

Chapter 4 Main Circuit TerminalsAFE2000 Series
Frame D
Main circuit terminals:
R(L1), S(L2), T(L3)
Max. Wire
Models
Gauge
AFE370A23A
AFE370A43A
300MCM
AFE450A43A
(152mm
AFE750A43A
UL installations must use 600V, 75℃ or 90℃ wire. Use copper wire only.
DC+ & DC-: must use 1kV Wire.
NOTE
Terminal r1/l1, s1/l2, t1/l3:
Wire Gauge: 22AWG [0.3mm²] ~ 16 AWG [1.3mm²]
Torque: 5 kg-cm [4.3 lb-in.] (0.49 N.m)
If additional terminal is needed when wiring, please refer to Figure 1 for
additional terminal dimension.
After crimping the wire to the ring lug please apply the UL approved R/C
(YDPU2) heat shrink tubing rate min 600Vac to the terminal. The insulation shall
be all over the live part. Please refer to Figure 2.
Figure 1
4-16
, DC+, DC-,
Min. Wire Gauge
250MCM (127mm
1/0 AWG (53.5mm
2
)
2/0 AWG (67.4mm
300MCM (152mm
Torque
(±10%)
2
)
M8
2
)
200kg-cm
2
)
(173 lb-in.)
2
(19.62Nm)
)
Figure 2

Hide quick links: