Delta Electronics AFE075A43A User Manual page 21

Afe2000 series. active front end unit
Table of Contents

Advertisement

Terminals
SG+
PIN 1,2,7,8 :Reserved
PIN 4: SG-
SG-
Multi-function relay output 1 (N.O.)
RA1
a
Multi-function relay output 1 (N.C.)
RB1
b
RC1
Multi-function relay common
RA2
Multi-function relay output 2 (N.O.) a
RB2
Multi-function relay output 2 (N.C.) b
RC2
Multi-function relay common
Digital inputs (FWD, REV, MI1~MI8, COM)
When using contacts or switches to control the digital inputs, please use high quality
components to avoid contact bounce.
Transistor outputs (MO1, MO2, MCM)
 Make sure to connect the digital outputs to the right polarity.
When connecting a relay to the digital outputs, connect a surge absorber across the coil and
check the polarity.
Removing the Terminal Block
1. Loosen the screws by screwdriver. (As shown in the figure.)
2. Remove the control board by pulling it out in parallel direction for 6~8 cm (as indicated in the figure
below : arrow 1) then lift the control board (as indicated in the figure below: arrow 2).
Terminal Function
PIN 3, 6: GND
PIN 5: SG+
NOTE: Wire size of analog control signals: 18 AWG (0.75 mm
Chapter 5 Control TerminalsAFE2000 Series
Factory Setting (NPN mode)
Resistive Load:
5A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
Inductive Load (COS 0.4):
2.0A(N.O.)/1.2A(N.C.) 250VAC
2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as drive is
in operation, frequency attained or overload indication.
5-19
2
) with shielded wire

Hide quick links: