Chapter 7 Option CardsAFE2000 Series
CMC-DN01
Functions
1.
Based on the high-speed communication interface of Delta HSSP protocol, able to conduct immediate
control to AFE2000 unit.
2.
Supports Group 2 only connection and polling I/O data exchange.
3.
For I/O mapping, supports Max. 32 words of input and 32 words of output.
4.
Supports EDS file configuration in DeviceNet configuration software.
5.
Supports all baud rates on DeviceNet bus: 125kbps, 250kbps, 500kbps and extendable serial
transmission speed mode.
6.
Node address and serial transmission speed can be set up on AFE2000 unit.
1.
Power supplied from AFE2000 unit.
Product Profile
Specifications
DeviceNet Connector
Interface
Transmission method
Transmission cable
Transmission speed
Network protocol
AFE2000 Connection Port
Interface
Transmission method
Terminal function
Communication protocol
5-PIN open removable connector. Of 5.08mm PIN interval
CAN
Shielded twisted pair cable (with 2 power cables)
125kbps, 250kbps, 500kbps and extendable serial transmission speed mode
DeviceNet protocol
50 PIN communication terminal
SPI communication
1. Communicating with AFE2000 unit
2. Transmitting power supply from AFE2000 unit
Delta HSSP protocol
7-48
1. NS indicator
2. MS indicator
3. POWER indicator
4. Positioning hole
5. DeviceNet connection port
6. Screw fixing hole
7. Fool-proof groove
8. AFE2000 connection port

Hide quick links: