11. OPTIONS AND PERIPHERAL EQUIPMENT
Calculate the energy at different timings in one cycle. Energy is a positive value in power running and a
negative value in regeneration. Write down the energy during power running/regeneration with signs in
the calculation table as shown below.
Timing
1)
A-axis
E1A
B-axis
E1B
C-axis
E1C
Sum
E1
Calculate the energy consumed by the regenerative resistor with the following equation for the
calculation results from E1 to E11 with a negative value.
When the absolute value of the value in E1 to E11 is assumed to be Es: ER [J] = η
If ER values are negative at all timings, the regenerative option is not needed. If any of ER values is
positive, calculate the energy consumed by the regenerative resistor in one cycle from the time for one
cycle and the sum of the positive ER values.
PR [W] = Sum of the positive ER values/Operating time (tf) for one cycle
Regenerative option is not required when PR is equal to or less than the specification value of the servo
amplifier built-in regenerative energy.

11.2.3 Parameter setting

Set [Pr. PA02] according to the option to be used.
2)
3)
4)
E2A
E3A
E4A
E2B
E3B
E4B
E2C
E3C
E4C
E2
E3
E4
[Pr. PA02]
0 0
Regenerative option selection
: Regenerative option is not used. (Built-in regenerative resistor is used.)
00
: MR-RB3N
0B
: MR-RB14
0D
: MR-RB34
0E
11 - 10
5)
6)
7)
E5A
E6A
E7A
E5B
E6B
E7B
E5C
E6C
E7C
E5
E6
E7
8)
9)
10)
E8A
E9A
E10A
E8B
E9B
E10B
E8C
E9C
E10C
E8
E9
E10
• Es - Ec
m
11)
E11A
E11B
E11C
E11