11.10 Earth-leakage current breaker

(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select an earth-leakage current breaker according to the following formula, and ground the servo
amplifier, servo motor, etc. securely.
To minimize leakage currents, make the input and output wires as short as possible, and keep a
distance of 30 cm or longer between the wires and ground.
Rated sensitivity current ≥ 10 • {Ig1 + Ign + Iga + K • (Ig2 (A-axis) + Igm (A-axis) + Ig2 (B-axis) + Igm
Ig1
: Leakage current on the electric channel from the earth-leakage current breaker to the input
Ig2
terminals of the servo amplifier (Found from Fig. 11.1.)
Ign
: Leakage current on the electric channel from the output terminals of the servo amplifier to the
Iga
servo motor (Found from Fig. 11.1.)
Igm
: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF)
: Leakage current of the servo amplifier (Found from table 11.3.)
: Leakage current of the servo motor (Found from table 11.2.)
Fig. 11.1 Leakage current example (lg1, lg2) for CV cable run in metal conduit
Wire
NV
Noise filter
Servo
amplifier
Ig1
Ign
Iga
120
100
80
60
40
20
0
2
3.5 8
Cable size [mm ]
Table 11.2 Servo motor's leakage current example (lgm)
Servo motor power [kW]
(B-axis) + Ig2 (C-axis) + Igm (C-axis))} [mA].........(11.1)
Wire
Earth-leakage current breaker
M
A-axis
Ig2
Igm
Wire
B-axis
M
Models provided with
harmonic and surge
Ig2
Igm
reduction techniques
Wire
C-axis
M
General models
Ig2
Igm
5.5 14
38100
22
60 150
30
80
2
0.05 to 1
11 - 39
Mitsubishi
Type
Electric
products
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
BV-C1
NFB
NV-L
Leakage current [mA]
0.1
K
1
3