3. SIGNALS AND WIRING
3.3.2 Power-on sequence
(1) Power-on procedure
1) Always wire the power supply as shown in above section 3.1 using the magnetic contactor with
the main circuit power supply ((L1/L2/L3)). Configure up an external sequence to switch off the
magnetic contactor as soon as an alarm occurs in all axes of A, B, and C.
2) Switch on the control circuit power supply (L11/L21) simultaneously with the main circuit power
supply or before switching on the main circuit power supply. If the control circuit power supply is
turned on with the main circuit power supply off, and then the servo-on command is transmitted,
[AL. E9 Main circuit off warning] will occur. Turning on the main circuit power supply stops the
warning and starts the normal operation.
3) The servo amplifier receives the servo-on command within 4 s after the main circuit power supply
is switched on.
(Refer to (2) in this section.)
(2) Timing chart
Main circuit
Control circuit
Base circuit
Servo-on command
(from controller)
Note 1. This range will be approximately 6 s for the linear servo system and fully closed loop system.
2. The time will be longer during the magnetic pole detection of a linear servo motor and direct drive motor.
POINT
An output signal, etc. may be irregular at power-on.
Servo-on command accepted
(Note 1)
ON
power supply
OFF
ON
OFF
ON
OFF
(4 s)
95 ms
(Note 2)
3 - 10
10 ms
95 ms