Setting The Current Limits - Siemens SITRANS P300 Operating Instructions Manual

With hart communication
Table of Contents

Advertisement

See also
Error display (Page 6-6)
7.12

Setting the current limits

Description
The level of the upper and lower fault current and the upper and lower saturation limits can
be freely selected within the preset limits of the current output signal.
The specified accuracy of the current output signal is only valid within the current limits 4 to
20 mA.
Figure 7-10
(1)
(2)
(3)
(4)
(5)
(6)
(7)
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02
Current limits
Linear control range
Lower saturation limit (default value)
Upper saturation limit (default value)
Lower fault current value (default value)
Upper fault current value (default value)
Recommended setting range for lower fault current range and lower control range limit
Recommended setting range for upper fault current range and upper control range limit
Operating functions via HART
7.12 Setting the current limits
7-19