6.5.2

Local operation without digital display

Introduction
Devices with a cover without an inspection window are supplied without digital display and
with key lock. If the device does not have a digital display or key lock, limited operation via
the keys is still possible depending on the lock mode.
Setting/adjusting zero point/limit point without digital display
You can set or adjust the zero and limit points without a digital display. Further modes can
no longer be selected.
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02
Mode
Key function
<MODE> <UP>
<DOWN> <UP> and
10
Switching between
the five functions
11
Select "lin" in case
another adjustment
was made.
12
13
Select from three
options.
14
Select from the table
for measured values
display.
Display, explanations
<DOWN>
0
None
LA
all locked
LO
all locked except for zero point
LS
all locked except for zero point and
limit point
L
Write protection
Operation via HART not possible.
linear
lin
linear
If you have reached this mode, you have
presumably not selected "lin" in mode 11.
Select "lin".
Display type (input value)
Output current in mA
Measured value in %
In each case
Physical unit
the first value
from the table
of the physical
unit
Operation
6.5 Local operation
6-11