6.5 Local operation
"Setting" requirement
You are familiar with the correct operation of the transmitter and the associated safety
information.
Setting electrical damping
To set the electrical damping to 0 seconds, proceed as follows:
1. Set mode 4.
2. Press the keys <UP> and <DOWN> simultaneously.
3. Save with the <MODE> key.
Result
Electrical damping is set to 0 seconds.
"Adjusting" requirement
The basic calibration of the steps is a 0.1 second interval. The longer you depress the <UP>
and <DOWN> key, the greater the steps.
Adjusting electrical damping
To adjust the electrical damping, proceed as follows:
1. Set mode 4.
2. Adjust the desired damping.
3. Save with the <MODE> key.
Result
Electrical damping has been adjusted to the desired time constant.
See also
Operating via keys (Page 6-12)
6-20
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02