Operation
6.4 Digital display
6.4.3
Error display
Description
If hardware faults, software errors or diagnostic alarms occur in the transmitter, the message
"Error" appears in the measured value display.
A ticker appears in the lower line of the digital display indicating the type of error. This
diagnostic information is also available via HART communication.
Display
Figure 6-3
The following messages may appear as a ticker in the bottom line of the digital display.
Ticker
"HARDWARE FIRMWARE ALARM"
"DIAGNOSTIC ALARM"
"SENSOR BREAK"
6-6
Example of error message
Meaning
Contains hardware faults such as:
incorrect checksum
•
incorrect EEPROM data
•
defective EEPROM
•
RAM fault
•
ROM fault
•
inconsistent data
•
EEPROMs not initialized
•
Is always displayed if
an event configured by the user is to be
•
signaled with an alarm.
For example:
Limit reached
–
Event counter for limit values exceeded
–
Calibration time expired
–
Current saturation reached
–
the status of one of the device variables is
•
"BAD".
Appears when there is a sensor break.
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02