Error Display - Siemens SITRANS P300 Operating Instructions Manual

With hart communication
Table of Contents

Advertisement

Operation
6.4 Digital display
6.4.3

Error display

Description
If hardware faults, software errors or diagnostic alarms occur in the transmitter, the message
"Error" appears in the measured value display.
A ticker appears in the lower line of the digital display indicating the type of error. This
diagnostic information is also available via HART communication.
Display
Figure 6-3
The following messages may appear as a ticker in the bottom line of the digital display.
Ticker
"HARDWARE FIRMWARE ALARM"
"DIAGNOSTIC ALARM"
"SENSOR BREAK"
6-6
Example of error message
Meaning
Contains hardware faults such as:
incorrect checksum
incorrect EEPROM data
defective EEPROM
RAM fault
ROM fault
inconsistent data
EEPROMs not initialized
Is always displayed if
an event configured by the user is to be
signaled with an alarm.
For example:
Limit reached
Event counter for limit values exceeded
Calibration time expired
Current saturation reached
the status of one of the device variables is
"BAD".
Appears when there is a sensor break.
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02