"Mass", "Volume of flow" and "Mass of flow" are marked as inactive and are given the status
CONSTANT.
Description
Figure 7-4
Measurement type "User"
DV
Device Variable
PV
Primary Variable
SV
Secondary Variable
TV
Tertiary Variable
QV
Quarternary Variable
The first function, "Input scaling, pressure", defines here too the pressure range which is
used by the customized characteristic curve. Ideally, this range corresponds to the sensor
limits. In the calculation example, 0 and 2 bar are assumed. This means that with process
pressure of 0.5 bar, there is an input value of 25% on the characteristic curve.
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02
7.4 Selecting the measurement type
MA
Zero value
ME
Limit value
Operating functions via HART
7-9