Siemens SITRANS P300 Operating Instructions Manual page 66

With hart communication
Table of Contents

Advertisement

Operation
6.5 Local operation
Resetting fault current
To reset the fault current to the basic setting, proceed as follows:
Press the keys <UP> and <DOWN> simultaneously.
Fault causes
Fault currents may be triggered by:
• FW alarm
• HW alarm
• Diagnostic interrupt
• Sensor breakage
• Measured value status BAD
Reference
NAMUR recommendation NE43 of Jan 18 1994:
"Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal"
See also
Operating via keys (Page 6-12)
6-28
Note
If a current saturation alarm is active, the setting of the output current may deviate from
your setting in case of a fault.
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02