Communication
HART communication
Protocol
Software for computer
See also
SITRANS P300 gauge pressure / absolute pressure (Page 10-1)
9.2
SITRANS P300 gauge pressure / absolute pressure (flush-mounted)
Specifications
Input
Measured variable
Measuring span
•
•
•
•
•
Depending on the process connection, the
measuring span may differ from these values
Lower measuring limit
•
Upper measuring limit
•
Output
Output signal
•
•
•
•
•
•
SITRANS P300 with HART communication
Operating Instructions, 06/2005, A5E00359579-02
9.2 SITRANS P300 gauge pressure / absolute pressure (flush-mounted)
8 ... 250 mbar g (0.12 ... 3.6 psi g)
0.01 ... 1 bar g (0.15 ... 14.5 psi g)
0.04 ... 4 bar g (0.58 ... 58 psi g)
0.16 ... 16 bar g (2.3 ... 232 psi g)
0.6 ... 63 bar g (9.1 ... 914 psi g)
Measuring cell with silicone oil
Measuring cell with silicone oil
Lower limit (infinitely adjustable)
Upper limit (infinitely adjustable)
Ripple (without HART communication)
Electrical damping time constants (T
Current sensor
Failure signal
230 ... 1100 Ω
HART Version 5.x
SIMATIC PDM
Gauge pressure (flush-mounted)
Maximum permissible operating pressure
2 bar g (29 psi g)
4 bar g (58 psi g)
7 bar g (102 psi g)
21 bar g (305 psi g)
67 bar g (972 psi g)
30 mbar a (0.44 psi a)
100% of maximum measuring span
4 ... 20 mA
Set to 3.84 mA (min. 3.55 mA)
Set to 20.5 mA (max. 23 mA)
I
≤ 0.5% of maximum output current
SS
)
0 ... 100 s
63
3.55 mA ... 23 mA
3.55 mA ... 23 mA
Specifications
9-5