Installing PROFIBUS PA Devices
•
PROFIBUS PA must be terminated at both extreme ends of the cable for it to work properly.
•
Please refer to the
available from www.profibus.com, for information on installing PROFIBUS devices.
•
If a Weidmüller or other current limiting junction box is connected to this device, please
ensure that the current limit is set to 40 mA or higher..
Basic PLC configuration with PROFIBUS PA
active PLC
SITRANS
LR560 PA
Wiring setups for hazardous area installations
Wiring setups for hazardous area installations
See
Programming SITRANS LR560
Quick Start Wizard via the LDI push buttons
• See
Quick Start Wizard via SIMATIC PDM
• See
Activating SITRANS LR560
Power up the device. A transition screen showing first the Siemens logo and then the current
firmware revision is displayed while the first measurement is being processed. SITRANS LR560
automatically starts up in Measurement mode.
The first time the device is configured, you will be prompted to select a language (English,
German, French, Spanish or Chinese).
Local Display Interface (LDI)
Modify parameters using the LDI push buttons.
(Siemens infrared handheld programmer can be ordered
separately: [Part No. 7ML1930-1BK]).
7ML19985XQ81
SITRANS LR560 (PROFIBUS PA) – QUICK START MANUAL
PROFIBUS PA User and Installation Guidelines
PROFIBUS DP
PROFIBUS PA
SITRANS
LR560 PA
PDM
DP/PA
coupler
SITRANS
LR560 PA
on page 16
on page 11.
on page 14.
(order number 2.092),
PC/laptop
Page EN-9