Section 4 Detailed Setup - Fisher FIELDVUE DVC6200 Instruction Manual

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200:
Table of Contents

Advertisement

Instruction Manual
D103409X012

Section 4 Detailed Setup

Detailed Setup
Field Communicator
Configure > Detailed Setup (1‐2)
Note
Detailed Setup is available for instrument level HC, AD, PD, and ODV.
Detailed Setup allows you to configure the digital valve controller to your application. Table 4‐1 lists the default settings
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel
cutoffs and limits. You can also restart the instrument and set the protection.
Table 4‐1. Default Detailed Setup Parameters
Control Mode
Restart Control Mode
Zero Power Condition
Analog In Range Low
Analog In Range High
Analog Input Units
Feedback Connection
Travel Sensor Motion
Instrument
Configuration
Auxiliary Terminal Action
Max Supply Pressure
Pressure Units
Temperature Units
Polling Address
Burst Mode Enable
Burst Command
Cmd 3 Configured Pressure
Tuning Set
Input Characterization
Travel Limit High
Travel Limit Low
Travel/Pressure Cutoff High
Travel/Pressure Cutoff Low
Dynamic Response and
Tuning
Set Point Rate Open
Set Point Rate Close
Set Point Filter Time (Lag Time)
Integrator Enable
Integral Gain
Integral Deadzone
44
Setup Parameter
-continued on next page-
(1)
Default Setting
Analog
Resume Last
(2)
Valve Open
4 mA
20 mA
mA
(2)
Rotary - All
(2)
CW/To Bottom Inst.
Disabled
(2)
20
(3)
PSI
(3)
F
0
No
3
A-B
(2)
F
Linear
125%
-25%
99.46%
0.50%
0%/sec
0%/sec
0 sec
Yes
9.4 repeats/minute
0.26%
Detailed Setup
May 2013
47