Fisher FIELDVUE DVC6200f Instruction Manual

Fisher FIELDVUE DVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
r
Fisher
FIELDVUE
Controller for F
This manual applies to:
Device Type
Device Revision
Hardware Revision 8
Firmware Revision
DD Revision
Instrument Level
www.Fisher.com
DVC6200f Digital Valve
OUNDATION
4602
2
2.0
2 and 3
FD, PD, AD
DVC6200f Digital Valve Controller
™ fieldbus
July 2013

Advertisement

Table of Contents
loading

Summary of Contents for Fisher FIELDVUE DVC6200f

  • Page 1 Instruction Manual DVC6200f Digital Valve Controller D103412X012 July 2013 ™ Fisher FIELDVUE DVC6200f Digital Valve Controller for F ™ fieldbus OUNDATION This manual applies to: Device Type 4602 Device Revision Hardware Revision 8 Firmware Revision DD Revision 2 and 3...
  • Page 2 The FIELDVUE DVC6200f Digital Valve Controller is a core component of the PlantWeb™ digital plant architecture. The digital valve controller powers PlantWeb by capturing and delivering valve diagnostic data. Coupled with ValveLink™ software, the DVC6200 provides users with an accurate picture of valve performance, including actual stem position, instrument input signal, and pneumatic pressure to the actuator.
  • Page 3: Table Of Contents

    DVC6200f Digital Valve Controller D103412X012 July 2013 Contents Figure 1‐1. FIELDVUE DVC6200f Digital Valve Controller Section 1 Introduction and Specifications ..... .
  • Page 4 Instruction Manual DVC6200f Digital Valve Controller July 2013 D103412X012 Component Replacement ....Instrument Specific Blocks ....Removing the Module Base .
  • Page 5: Section 1 Introduction And Specifications

    DVC6200f digital valve controllers can be mounted on single or double‐acting sliding‐stem actuators, as shown in figure 1‐2, or on rotary actuators. It can also be integrally mounted to the Fisher GX control valve and actuator system, as shown in figure 1‐3. The DVC6200f mounts on most Fisher and other manufacturers' rotary and sliding‐stem...
  • Page 6 July 2013 D103412X012 Figure 1‐2 FIELDVUE DVC6200f Digital Valve Figure 1‐3. FIELDVUE DVC6200f Digital Valve Controller Mounted on a Fisher Sliding‐Stem Valve Controller Integrally Mounted to a Fisher GX Control Actuator Valve and Actuator System W9616_fieldbus W9643_fieldbus DVC6200f digital valve controllers are available with several selections of control and diagnostic capability. Control selections include: D Standard Control (SC)—...
  • Page 7 Instruction Manual Introduction and Specifications D103412X012 July 2013 Instrument Blocks The digital valve controller is a block‐based device. For detailed information on the blocks within the digital valve controller, see the Detailed Setup section of this manual. The DVC6200f digital valve controller includes the resource and transducer block: D Resource Block—The resource block contains the hardware specific characteristics associated with a device;...
  • Page 8: Using This Manual

    Instruction Manual Introduction and Specifications July 2013 D103412X012 Using This Manual Navigation paths and fast‐key sequences are included for procedures and parameters that can be accessed using the Field Communicator. For example, to access Resource Block Mode: RB > Configure/Setup > Setup > Resource Block Mode Field Communicator An overview of the resource and transducer block menu structures are shown in Appendix B.
  • Page 9 Available Mounting Fieldbus Device Capabilities Backup Link Master capable DVC6200f digital valve controller and DVC6215 feedback unit: J Integral mounting to the Fisher GX Control Valve and Actuator System J Integral Supply Pressure mounting to Fisher rotary actuators, J Sliding‐stem Minimum Recommended: 0.3 bar (5 psig) higher...
  • Page 10 Instruction Manual Introduction and Specifications July 2013 D103412X012 Table 1‐1. Specifications (continued) (1)(4) Operating Ambient Temperature Limits IECEx— IP66 -40 to 85_C (-40 to 185_F) Other Classifications/Certifications -52 to 85_C (-62 to 185_F) for instruments utilizing the Extreme Temperature option (fluorosilicone Natural Gas Certified, Single Seal Device—...
  • Page 11 Stainless steel (optional) Declaration of SEP Cover: Thermoplastic polyester Elastomers: Nitrile (standard) Fisher Controls International LLC declares this Fluorosilicone (extreme temperature) product to be in compliance with Article 3 paragraph 3 of the Pressure Equipment Directive (PED) 97 / 23 / Options EC.
  • Page 12: Related Information

    Other documents containing information related to the DVC6200f digital valve controller include: D Bulletin 62.1:DVC6200f—Fisher FIELDVUE DVC6200f Digital Valve Controller (D103399X012) D Bulletin 62.1:DVC6200f FD—Fisher FIELDVUE DVC6200f Digital Valve Controller (D103422X012) D Bulletin 62.1:DVC6200(S1)—Fisher FIELDVUE DVC6200 Digital Valve Controller Dimensions (D103543X012) D Fisher FIELDVUE DVC6200 Series Quick Start Guide (D103556X012) D 475 Field Communicator User's Manual...
  • Page 13: Section 2 Installation

    The DVC6200f housing is available in two different configurations, depending on the actuator mounting method. Figure 2‐1 shows the available configurations. Figure 2‐1. Housing Configurations HOUSING FOR HOUSING FOR LINEAR AND ROTARY ACTUATORS FISHER GX ACTUATORS INTEGRAL OUTPUT PRESSURE PORT ROTARY NAMUR, M6 HOLE FOR LINEAR, M8...
  • Page 14 Instruction Manual Installation July 2013 D103412X012 The feedback system for the DVC6200f digital valve controller utilizes a magnetic assembly for linkage‐less, non‐contacting position measurement. In order to prevent inadvertent stem movement while the instrument is in operation, magnetic tools (such as a magnetic‐tipped screwdriver) should not be used. Note The magnet assembly may be referred to as a magnetic array in user interface tools.
  • Page 15 Each mounting kit includes detailed information on mounting the digital valve controller to a specific actuator. Refer to table 2‐1 for the more common Fisher actuator mounting instructions, available at www.fisher.com or your Emerson Process Management sales office.
  • Page 16: Dvc6205F Base Unit

    Installation July 2013 D103412X012 For general mounting guidelines, refer to the DVC6200 Series quick start guide (D103556X012), available at www.fisher.com or your Emerson Process Management sales office. Table 2‐1. FIELDVUE DVC6200f Mounting Instructions Instructions for Mounting: Part Number 585C/585CR Size 25 Actuator with or without Handjack...
  • Page 17 Instruction Manual Installation D103412X012 July 2013 Figure 2‐4. FIELDVUE DVC6205f Base Unit with Mounting Bracket (Rear View) 10C1796‐A Figure 2‐5. FIELDVUE DVC6205f Base Unit Wall Mounting SPACER 1‐INCH 1/4‐20 HEX HEAD SCREW MOUNTING BRACKET X0428...
  • Page 18: Dvc6215 Feedback Unit

    (such as a magnetic‐tipped screwdriver) should not be used. Figure 2‐7. Feedback Unit Housing Configurations HOUSING FOR HOUSING FOR LINEAR AND ROTARY ACTUATORS FISHER GX ACTUATORS INTEGRAL OUTPUT PRESSURE PORT ROTARY NAMUR, M6 HOLES FOR LINEAR, M8...
  • Page 19 Instruction Manual Installation D103412X012 July 2013 CAUTION The magnet assembly material has been specifically chosen to provide a long‐term stable magnetic field. However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet placed in close proximity (less than 25 mm) can cause permanent damage.
  • Page 20: Sliding-Stem Linear Actuators Up To 210 Mm (8.25 Inches) Travel

    However, despite subtle differences in fasteners, brackets, and connecting linkages, the procedures for mounting can be categorized as follows: D Sliding‐stem linear actuators D Fisher rotary actuators D GX actuator D Quarter‐turn actuators See figure 2‐3 for examples of the different travel feedback magnet assemblies.
  • Page 21 5. Align the magnet assembly as follows: For air‐to‐open actuators (e.g. Fisher 667) vertically align the magnet assembly so that the center line of the alignment template is lined up as close as possible with the upper extreme of the valid travel range on the magnet assembly. The magnet assembly should be positioned so that the index mark in the feedback slot of the DVC6215 housing is within the valid range on the magnet assembly throughout the range of travel.
  • Page 22: Fisher Rotary Actuators And Sliding-Stem Linear Actuators Over 210 Mm (8.25 Inches) Travel

    Ensure that there is clearance between the magnet assembly and the DVC6215 housing slot throughout the full range of travel. Fisher Rotary Actuators and Sliding‐Stem Linear Actuators over 210 mm (8.25 Inches) Travel The DVC6215 feedback unit uses a cam (designed for linear response) and roller as the feedback mechanism. See figures 2‐12 and 2‐13.
  • Page 23 Instruction Manual Installation D103412X012 July 2013 2. Verify that the appropriate cam is installed on the actuator as described in the instructions included with the mounting kit. 3. Mount the DVC6215 on the actuator as follows: D If required, a mounting adaptor is included in the mounting kit. Attach the adaptor to the feedback unit, then attach the feedback unit assembly to the actuator.
  • Page 24: Gx Actuators

    Instruction Manual Installation July 2013 D103412X012 Sliding‐Stem Linear Actuators over 210 mm (8.25 Inches) Travel Refer to the following guidelines when mounting on sliding‐stem linear actuators over 210 mm (8.25 inches) travel (see figure 2‐13). 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator.
  • Page 25 Instruction Manual Installation D103412X012 July 2013 Figure 2‐15. Air‐to‐Open Fisher GX Magnet Assembly Figure 2‐16. Air‐to‐Close Fisher GX Magnet Assembly Alignment Alignment ALIGNMENT TEMPLATE ALIGNMENT TEMPLATE RETAINING RETAINING SLOT SLOT INDEX MARK INDEX MARK W9219 W9218 5. Tighten the fasteners and remove the alignment template. Continue on with the appropriate step 6 below.
  • Page 26 Instruction Manual Installation July 2013 D103412X012 Figure 2‐17. Modifications for Fisher GX Actuator; Air‐to‐Open Construction Only PNEUMATIC TUBING FROM THE DVC6205f PNEUMATIC PORT INSTALL O‐RING X0128 Air‐to‐Close GX Actuators 6. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad.
  • Page 27: Quarter-Turn Rotary Actuators

    Instruction Manual Installation D103412X012 July 2013 Quarter‐Turn Rotary Actuators The DVC6215 feedback unit can be mounted to any quarter‐turn rotary actuator, as well as those that comply with the NAMUR guidelines. A mounting bracket and associated hardware are required. Refer to figure 2‐18. 1.
  • Page 28: Fisher 67Cfr Filter Regulator

    Attach the 67CFR filter regulator to the side of the digital valve controller. Thread a 1/4‐inch socket‐head pipe plug into the unused outlet on the filter regulator. This is the standard method of mounting the filter regulator. Figure 2‐20. Mounting the Fisher 67CFR Regulator on a FIELDVUE DVC6200f Digital Valve Controller 67CFR CAP SCREWS O‐RING...
  • Page 29: Supply

    Instruction Manual Installation D103412X012 July 2013 Figure 2‐21. Pressure Connections LOOP CONNECTIONS TERMINAL BOX 1/2 NPT CONDUIT WIRING CONNECTION TERMINAL BOX OUTPUT A CONNECTION SUPPLY CONNECTION FEEDBACK CONNECTIONS OUTPUT B W9615-fieldbus TERMINAL BOX CONNECTION X0379-fieldbus DVC6205f BASE UNIT VALVE MOUNTED UNIT Supply WARNING To avoid personal injury or property damage resulting from bursting or parts, do not exceed maximum supply pressure.
  • Page 30: Output Connection

    Instruction Manual Installation July 2013 D103412X012 D Ensure that the cover is correctly installed before putting this unit back into service. Failure to do so could result in personal injury or property damage from fire or explosion. The DVC6200f can be used with air or natural as as the supply medium. If using natural gas as the pneumatic supply medium, natural gas will be used in the pneumatic output connections of the DVC6200f to any connected equipment.
  • Page 31: Special Construction To Support Solenoid Valve Testing

    Instruction Manual Installation D103412X012 July 2013 Double‐Acting Actuators DVC6200f digital valve controllers on double‐acting actuators always use relay A. With no instrument Fieldbus power (Zero Power Condition) OUTPUT A is at 0 pressure and OUTPUT B is at full supply pressure when the relay is properly adjusted.
  • Page 32: Vent

    Instruction Manual Installation July 2013 D103412X012 Vent WARNING Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent opening is open and free of debris to prevent pressure buildup under the cover. WARNING This unit vents the supply medium into the surrounding atmosphere.
  • Page 33: Wiring And Electrical Connections

    Instruction Manual Installation D103412X012 July 2013 Wiring and Electrical Connections Connecting Fieldbus Wiring The digital valve controller is normally powered over the bus from a fieldbus power supply. Refer to the site planning guide for proper wire types, termination, length, etc. for a fieldbus loop. Note As shipped from the factory, the DVC6200f digital valve controller will not move the valve when power is applied to the instrument.
  • Page 34: Twisted-Shielded Pair

    Instruction Manual Installation July 2013 D103412X012 Twisted Shielded Pair Refer to figure 8‐2 for identification of parts. Wire the digital valve controller as follows, refer to figure 2‐24: Figure 2‐24. Loop Connections Terminal Box SAFETY TALK GROUND TALK EARTH GROUND LOOP LOOP GE41456-A...
  • Page 35: Quick Connect Cable Entry

    Instruction Manual Installation D103412X012 July 2013 5. Replace and hand tighten the cover on the terminal box. To secure the terminal box cap engage the lock screw. When the loop is ready for startup, apply power to the H1 card output. Quick Connect Cable Entry The DVC6200f is offered with a quick connect cable entry option, shown in figure 2‐25, for the fieldbus...
  • Page 36: Remote Travel Sensor Connections

    Instruction Manual Installation July 2013 D103412X012 e. The instrument is not polarity sensitive. Refer to figure 2‐24. Connect the blue wire to one of the LOOP terminals in the terminal box. Connect the brown wire to the other LOOP terminal. Cut the green/yellow wire off inside of the DVC6200f, and ensure that the shield is totally isolated at the instrument end.
  • Page 37 Instruction Manual Installation D103412X012 July 2013 Figure 2‐26. Terminal Details for Connecting the Base Unit and Feedback Unit for Remote‐Mounted Digital Valve Controllers FEEDBACK CONNECTIONS TERMINAL BOX X0131-FF FEEDBACK UNIT GROUND BASE UNIT SCREW TO FEEDBACK UNIT TERMINAL 1 TO FEEDBACK UNIT TERMINAL 2 TO FEEDBACK UNIT TERMINAL 3 TO FEEDBACK UNIT TERMINAL 4 TO FEEDBACK UNIT TERMINAL S...
  • Page 38: Communication Connections

    Instruction Manual Installation July 2013 D103412X012 Figure 2‐27. Secure Wires in Clips CLIP TO SUPPORT THE WIRES OF THE 4-CONDUCTOR SHIELDED CABLE CLIP TO SUPPORT THE INSULATED SHIELD WIRE Communication Connections WARNING Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially explosive atmosphere or in an area that has been classified as hazardous.
  • Page 39: Commissioning Tag

    Instruction Manual Installation D103412X012 July 2013 Commissioning Tag The DVC6200f digital valve controller is supplied with a removable paper commissioning tag, shown in figure 2‐28. This tag contains both the device ID and a space to record the device's tag number. The device ID is a unique code that identifies a particular device in the absence of a device tag.
  • Page 40 Instruction Manual Installation July 2013 D103412X012...
  • Page 41: Section 3 Basic Setup

    Instruction Manual Basic Setup D103412X012 July 2013 Section 3 Basic Setup3-3- Basic Setup Field Communicator TB > Configure/Setup > Basic Setup WARNING Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application, these changes may upset process control, which may result in personal injury or property damage.
  • Page 42: Device Setup

    Instruction Manual Basic Setup July 2013 D103412X012 Device Setup Field Communicator TB > Configure/Setup > Basic Setup > Device Setup Follow the prompts on the Field Communicator display to automatically setup the instrument using specified actuator information. Table 3‐2 provides the actuator information required to setup and calibrate the instrument. Note If reverse‐acting relay B is used, you must manually set the Relay Type (BASIC_SETUP.RELAY_TYPE [42.5]) to B.
  • Page 43 (Window-mount) 60, 70 Depends upon pneumatic connections. See 1061 Piston Dbl w/o Spring description for Travel Sensor Motion Fisher 68, 80, 100, 130 Mounting Style Travel Sensor Motion Away from the top of the instrument Towards the top of the...
  • Page 44 Relay A adjustment may be required before Device Setup can determine travel sensor motion. Follow the prompts on the Field Communicator display if relay adjustment is necessary. Table 3‐2 lists the required Travel Sensor Motion selections for Fisher and Baumann actuators.
  • Page 45 Stabilize/Optimize or Performance Tuner may be used to achieve the desired results more rapidly than expert tuning. Table 3‐2 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are only recommended starting points. After you finish setting up and calibrating the instrument, use Stabilize/Optimize to...
  • Page 46: Performance Tuner

    Instruction Manual Basic Setup July 2013 D103412X012 When Device Setup is complete you are asked if you wish to run Auto Calibration now. Select yes to automatically calibrate instrument travel at this time. Follow the prompts on the Field Communicator display. The calibration procedure uses the valve and actuator stops as the 0% and 100% calibration points.
  • Page 47: Section 4 Detailed Setup

    Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 Section 4 Detailed Setup 4-4- Resource Block Overview The resource block contains the hardware specific characteristics associated with a device; it has no input or output parameters. The resource block monitors and controls the general operation of other blocks within the device. Most of the resource block parameters are operational parameters that provide information about the instrument such as identification, hardware information, available options, etc.
  • Page 48 Instruction Manual Detailed Setup—Resource Block July 2013 D103412X012 D Write Priority Write Priority (WRITE_PRI [39]) sets the priority for Write Alarm. The lowest priority is 0. The highest is 15. Communication Time Out RB > Configure/Setup > Communication Time Out Field Communicator D Shed Remote Cascade Note Typically this parameter does not need to be changed.
  • Page 49 Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 D Miscellaneous Options Miscellaneous Options (MISC_OPTIONS [46]) indicates which miscellaneous licensing options are enabled. D Features Available Features Available (FEATURES [17]) indicates which Resource Block Options features are available. d Reports—Reports enables alert and event reporting. Reporting of specific alerts may be suppressed. See Alerts on page 69.
  • Page 50 D Manufacturer—Manufacturer Identification (MANUFAC_ID [10]) identifies the manufacturer of the instrument. It is used by the host system to locate the DD file for the device. For Fisher the Manufacturer ID is 0x5100. D Device Type—Device Type (DEV_TYPE [11]) identifies the type of device. It is used by the host system to locate the...
  • Page 51 Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 D Diagnostic Options—Diagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the instrument. Version RB > Configure/Setup > Version Field Communicator D Device Revision—The Device Revision (DEV_REV [12]) is the manufacturer's revision number associated with the resource, used by an interface device to locate the DD file for the resource.
  • Page 52 Instruction Manual Detailed Setup—Resource Block July 2013 D103412X012 Table 4‐2. Parameters Affected by Restart with Table 4‐2. Parameters Affected by Restart with Defaults Defaults (Continued) Index Index Parameter Name Initial Value Parameter Name Initial Value Number Number AO Block (continued) Resource Block FSTATE_TIME ST_REV...
  • Page 53 Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 Table 4‐2. Parameters Affected by Restart with Table 4‐2. Parameters Affected by Restart with Defaults (Continued) Defaults (Continued) Index Index Parameter Name Initial Value Parameter Name Initial Value Number Number PID Block (continued) PID Block (continued) OUT_HI_LIM BIAS...
  • Page 54 Instruction Manual Detailed Setup—Resource Block July 2013 D103412X012 Table 4‐2. Parameters Affected by Restart with Table 4‐2. Parameters Affected by Restart with Defaults (Continued) Defaults (Continued) Index Index Parameter Name Initial Value Parameter Name Initial Value Number Number ISEL Block (continued) ISEL Block (continued) DISABLE_3 HI_HI_LIM...
  • Page 55 Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 Table 4‐2. Table Parameters Affected by Restart with Table 4‐2. Parameters Affected by Restart with Defaults (Continued) Defaults (Continued) Index Index Parameter Name Initial Value Parameter Name Initial Value Number Number OS Block (continued) MAI Block (continued) BKCAL_1_IN MODE_BLK...
  • Page 56 Instruction Manual Detailed Setup—Resource Block July 2013 D103412X012 Resource Block Parameter List D Read/Write Capability: RO - Read Only, RW - Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter. Table 4‐3.
  • Page 57 The device type directories contain files named by combining the device revision for the particular device type with the revision of the device description. The manufacturer id for Fisher is 0x005100. Data Type: Unsigned16 Device Type Manufacturer's model number associated with...
  • Page 58 Instruction Manual Detailed Setup—Resource Block July 2013 D103412X012 Table 4‐3. Resource Block Parameter Definitions (Continued) Label Index RO / Initial Mode Range Description PARAMETER_NAME Number Value 1: Reports Supported Data Type: Bit String 2: Fault State 0 = Inactive supported Features Selected 1 = Active 3: Software Write lock...
  • Page 59 Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 Table 4‐3. Resource Block Parameter Definitions (Continued) Label Index RO / Initial Mode Range Description PARAMETER_NAME Number Value Data Type: Unsigned32 Time duration (in 1/32 millisecond) at which to give up on computer writes to function block ROUT Timeout ROUT parameters.
  • Page 60 Instruction Manual Detailed Setup—Resource Block July 2013 D103412X012 Table 4‐3. Resource Block Parameter Definitions (Continued) Label Index RO / Initial Mode Range Description PARAMETER_NAME Number Value Data Type: Unsigned8 If set to Locked, no writes from anywhere are allowed except to clear WRITE_LOCK by entering 0=Undefined Write Lock Unlocked.
  • Page 61 Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 Table 4‐3. Resource Block Parameter Definitions (Continued) Label Index RO / Initial Mode Range Description PARAMETER_NAME Number Value Write Alarm WRITE_ALM Data Type: DS‐72 This alarm is generated when Unlocked in the 0=Undefined WRITE_LOCK parameter is set.
  • Page 62 Instruction Manual Detailed Setup—Resource Block July 2013 D103412X012 Table 4‐3. Resource Block Parameter Definitions (Continued) Label Index RO / Initial Mode Range Description PARAMETER_NAME Number Value Electronics Serial Number Data Type: Visible String Electronics serial Factory Set ELECTRONICS_SN number set by manufacturing. Factory Serial Number Data Type: Visible String spaces...
  • Page 63 Instruction Manual Detailed Setup—Resource Block D103412X012 July 2013 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information.
  • Page 64: Transducer Block

    Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Transducer Block Overview The transducer block accepts a signal from an output block as a set point to position a valve using a pneumatic actuator. Input to the transducer block is in percent. Closed is 0%, and open is 100%. The transducer block contains setup and calibration information and can be tuned to closely match the actuator.
  • Page 65 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 indicated in the Protect Category column of table 4‐14, to prevent inadvertently overwriting key data by the host system or user. d All— will protect all transducer block Parameters. d Setup and Calibration— will protect only Setup and Calibration transducer block parameters. d Calibration—...
  • Page 66 Stabilize/Optimize may be used to achieve the desired results more rapidly than Expert tuning. Table 3‐2 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either a higher or lower tuning set to get the desired response.
  • Page 67 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 If after completing initial setup and calibration the valve cycles or overshoots, or is sluggish, you can improve operation by running Stabilize/Optimize. Stabilize/Optimize is included with the device description (DD) firmware. Stabilize/Optimize is accessible from the transducer block and permits changing the transducer block set point a small amount to see if the valve is unstable or unresponsive.
  • Page 68 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐9. Gain Values for Preselected Pressure Tuning Sets Tuning Set Pressure Proportional Gain Pressure Integrator Gain Pressure Minor Loop Feedback Gain X (Expert) User Adjusted User Adjusted User Adjusted Note Use Expert tuning only if standard tuning has not achieved the desired results. Stabilize/Optimize may be used to achieve the desired results more rapidly than Expert tuning.
  • Page 69 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Note Travel / Pressure Select must be set to Travel for double acting actuators. Travel / Pressure Select (TVL_PRESS_SELECT [41.1]) determines if the instrument is setup for position or pressure control. Select Travel, Pressure, Travel with Pressure Fallback/Auto recovery or Travel with Pressure Fallback/Manual Recovery.
  • Page 70 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Custom Characterization Table TB > Configure/Setup > Detailed Setup > Response Control > Custom Characterization Table Field Communicator You can select from the three fixed input characteristics shown in figure 4‐1 or you can select a custom characteristic. Figure 4‐1 shows the relationship between the travel target and travel set point for the fixed input characteristics.
  • Page 71 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Outblock Selection TB > Configure/Setup > Detailed Setup > Response Control > Outblock Selection Field Communicator Outblock Selection (OUTBLOCK_SEL [96]) defines which output function block will control the setpoint of the valve. The output block that is not selected will shed its mode to reflect that it does not have control of the valve.
  • Page 72 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 mode is placed Out of Service. The instrument will attempt to drive the valve to the Zero Power Condition and will no longer execute transducer control function. D Drive Current Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or disabling Automatic recovery from Self Test Shutdown.
  • Page 73 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 remain Out of Service until power is removed and restored or the user changes the transducer block target mode to Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or until the shutdown trigger is disabled.
  • Page 74 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 mode is placed out of service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute transducer control function. D Output Block Timeout Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or disabling Manual recovery from Self Test Shutdown.
  • Page 75 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 D Pressure A Sensor Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self Test Shutdown. When enabled, and the Port A Pressure Sensor Alert is active, the transducer Actual mode is placed out of service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute transducer control function.
  • Page 76 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 D Supply Pressure Lo Alert Enable—When enabled Supply Pressure Lo Alert Enable activates Supply Pressure Lo Alert. D Supply Pressure Lo Alert Point—Supply Pressure Lo Alert Point (SUP_PRES_LO_ALRT_PT [76.9]). When the supply pressure falls below the supply pressure alert point, the supply pressure alert is active. To disable the supply pressure alert, set Supply Pressure Alert Point to zero.
  • Page 77 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 D Travel Deviation Alert Point—The Travel Deviation Alert Point (TVL_DEV_ALRT_PT [77.1]) is the alert point for the difference, expressed in percent (%), between the travel target and the actual travel. When the difference exceeds the alert point for more than the Travel Deviation Time, the Travel Deviation Alert is set.
  • Page 78 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Figure 4‐3. Travel Lo Alert Deadband ALERT IS CLEARED TRAVEL ALERT DEADBAND TRAVEL ALERT LO POINT ALERT IS SET A6532‐1 Travel Hi/Lo D Travel Hi Alert—This alert is active if the Travel exceeds the Travel Hi Alert point. D Travel Hi Alert Enable—When enabled Travel Hi Alert Enable activates the Travel Hi Alert.
  • Page 79 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Travel Open D Travel Open Alert—This alert is active if the Travel is greater than the Travel Open Alert Point. D Travel Open Alert Enable—When enabled Travel Open Alert Enable activates the Travel Open Alert. D Travel Open Alert Point—Travel Open Alert Point (TVL_OPEN_ALRT_PT [77.8]) is the value of the travel in percent (%) or ranged travel, which, when exceeded, sets the Travel Open Alert.
  • Page 80 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Travel History Alerts TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts Field Communicator Cycle Counter D Cycle Counter—The Cycle Counter (CYCLE_COUNT [73]) records the number of times the travel changes direction. The change in direction must occur after the deadband has been exceeded before it can be counted as a cycle.
  • Page 81 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Figure 4‐5. Travel Accumulator Deadband (set at 10%) Deadband exceeded, new Reference Point established This amount of change is Deadband Reference added to the Travel Point Accumulator Deadband (+/- 5%) A6534 D Travel Accumulator Alert—This alert is active if the Travel Accumulator exceeds the Travel Accumulator Alert Point. The Travel Accumulator Alert is set when the Travel Accumulator value exceeds the Travel Accumulator Alert Point.
  • Page 82 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 PD Run PD Run enables or disables Performance Diagnostics in the instrument (PD Inside). Selecting PD Off disables PD Inside. Selecting PD On enables PD Inside. Performance Critical D Performance Critical Alert—This alert is active if the instrument is no longer able to control the valve or performance has been dramatically reduced.
  • Page 83 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 D Advise Suppress—Advise Suppress (ADVISE_MASK [67]) determines which of the advise alert conditions are suppressed so that they are not reported. Even if reporting is suppressed, the bit in Advise Active (ADVISE_ACTIVE [61]) is still set. Instrument TB >...
  • Page 84 Select from the drop‐down list or enter the manufacturer's identification number as defined by the Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100. D Valve Model Number—Enter the valve model number (VALVE_MODEL_NUM [26]), (design letter or type number) for the valve on which the instrument is mounted.
  • Page 85 Select from the drop‐down list or enter the manufacturer's identification number as defined by the Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100. D Actuator Model Number—Enter the type number for the actuator (ACT_MODEL_NUM [23]) on which the instrument is mounted.
  • Page 86 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid. Travel Sensor Motion (TRAVEL_SEN_MOTION [42.3]) establishes the proper valve travel sensor (feedback) rotation/movement.
  • Page 87 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐11. Output Block PV Status FEATURE_SEL Transducer Mode, Active PlantWeb AO / DO AO / DO AO/DO PV PW Alarms Set PV Status Actual Alarms PV Status PV Substatus Limit Substatus Device Failure Constant Non‐specific...
  • Page 88 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Alert Handling TB > Configure/Setup > Detailed Setup > Alert Handling Field Communicator PlantWeb Alert Simulate When enabled, PlantWeb Alert Simulate (PWA_SIMULATE [39]) allows the user to write to the following PlantWeb and Instrument alert parameters;...
  • Page 89 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Transducer Block Parameter List D Read/Write Capability: RO - Read Only, RW - Read Write D Mode: The block mode(s) required to write to the parameter D Protection Category: Indicates whether or not the parameter is writable while the PROTECTION parameter  is set to a particular level.
  • Page 90 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Update Event UPDATE_EVT 0=Undefined 1=Acknowledged UNACKNOWLEDGED NONE 2=Unacknowledged 0=Undefined Data Type: DS‐73 1=Updated reported UPDATE_STATE Alert generated by change to static...
  • Page 91 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Data Type: Float When the servo goes above this % of Travel Cutoff Hi span, the stem position goes to the -25 to 125 99.5...
  • Page 92 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Data Type: DS_66 SETPOINT_D is not updated unless SETPOINT_D the DO block is selected in FEATURE_SEL.
  • Page 93 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Data Type: DS‐65 PRESSURE_DIFF STATUS indicates the validity of Pressure Differential Status 38.1 VALUE.
  • Page 94 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Basic Setup BASIC_SETUP 1=Spring & Diaphragm 2=Piston‐Dbl w/o Spring Actuator Style 1=Spring & 42.1 SETUP Data Type: Enum (Uint8)
  • Page 95 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category TRAVEL_CAL Travel Count Data Type: Uint16 43.1 TVL_COUNT Raw feedback from Travel Sensor <TVL_FAC_HI Travel Hi Calibration Data Type: Uint16...
  • Page 96 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category TRAVEL_CAL_RUN 1: Operating 2: Autocalibrate 3: Not Used by DVC6200f 4: Mark Full Open 5: Mark Full Closed 6: Manual Calibrate Final 7: Abort...
  • Page 97 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category PRESS_CAL Supply Pressure Scale > 0 46.1 Data Type: Float SUPP_PRESS_SCALE Supply Pressure Offset 46.2 0 to 16383 Data Type: Uint16...
  • Page 98 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Data Type: Unit16 Array[43] Each item - 2500 to 12500 First integrator is number of valid points.
  • Page 99 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Advise Alarm Data Type: DS‐71 ADVISE_ALM Used to report alerts to host system 0=Undefined 1=Acknowledged UNACKNOWLEDGED...
  • Page 100 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category 0: Drive Current 1: Drive Signal 2: Processor Impaired 3: Output Block Timeout 4: Blocks Set to Defaults 5: Travel Sensor 6: Outlet Pressure Sensor 7: Supply Pressure...
  • Page 101 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Data Type: Bit String (4 byte) 0=disable 1=enable Maintenance alert mask. MASK controls whether an alert is Maintenance Suppress Same as for...
  • Page 102 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category INST_ALERTS_ACTIVE 0: Drive Current 1: Drive Signal 2: Memory Failure - Data Type: Bit String (4 byte) Pending Electronics Active 0=inactive...
  • Page 103 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category 0: I/P Primary Plugged 1: I/P Nozzle Plugged 2: I/P Latched 3: Reserved 4: Relay Jammed 5: Relay Cross Misadj 6: Relay Bias Diaph Leak 7: Relay Port A Diaph Leak...
  • Page 104 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category 0: Relay Disengaged 1: Insufficient Pressure Differential 2: Travel Calibration Error 3: Reserved 4: High Supply Pressure* 5: Reserved Data Type: Bit String (4 byte)
  • Page 105 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category INST_ALERTS_ENABLE Enabled Bits: 0: Drive Current 0: Drive Current 1: Drive Signal 1: Drive Signal 2: Program Data Type: Bit String (4 byte) 2: Program Memory...
  • Page 106 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category INST_ALERTS_CONFIG 0: Drive Current 1: Program Memory 2: Static Memory Data Type: Bit String (4 byte) 3: Processor or I/O 0=attempt control, Shutdown Trigger...
  • Page 107 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Data Type: Float Travel Open Alert Point Alert when valve is open. Control DI 77.8 -25% to 125% 99.5%...
  • Page 108 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category All bits: 0 Data Type: Bit String (2 byte) 2: Integrator Limited Low 0=inactive 3: Integrator Limited 1=active...
  • Page 109 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Reserved AI Data Type: Uint16 SETUP RESERVED_AI Reserved Upgrade Progress Data Type: Enum (Uint8) UPGRADE_PROGRESS Not used by the DVC6200f SPEC_SHEET_VALVE...
  • Page 110 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category SPEC_SHEET_ACT Actuator Size 85.1 NULL Data Type: Visible String ACTUATOR SIZE Effective Area 85.2 0.00 Data Type: Float...
  • Page 111 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category PERF_DIAG PD Run 1=PD On Data Type: Enum AUTO 88.1 1=PD On NONE PD_COMMAND 2=PD Off...
  • Page 112 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐14. Transducer Block Parameter Definitions (Continued) Label Index RO / Protect Mode Range Initial Value Description PARAMETER_NAME Number Category Bit 0: Travel feedback sensor detected Bit 1: Output Block Scheduled Block Information Bit 2: Trigger Capturing Data Type: Bit String (2 bytes) BLOCK_INFO...
  • Page 113 Instruction Manual Detailed Setup—Transducer Block D103412X012 July 2013 Note Because individual views are limited in size, View Lists 3 and 4 have multiple parts. Table 4‐17. Transducer Block, View 3.1 Table 4‐18. Transducer Block, View 3.2 Index Number Parameter Index Number Parameter ST_REV ST_REV...
  • Page 114 Instruction Manual Detailed Setup—Transducer Block July 2013 D103412X012 Table 4‐20. Transducer Block, View 4.2 Table 4‐21. Transducer Block, View 4.3 (continued) Index Number Parameter Index Number Parameter ST_REV ADVISE_MASK VALVE_SN FAILED_PRI VALVE_TYPE MAINT_PRI XD_CAL_LOC ADVISE_PRI XD_CAL_DATE XD_CAL_WHO Table 4‐22. Transducer Block, View 4.4 TEMPERATURE_UNITS Index Number Parameter...
  • Page 115: Analog Output Function Block

    Instruction Manual Detailed Setup—AO Function Block D103412X012 July 2013 Analog Output Function Block Overview The Analog Output (AO) function block (figure 4‐6) assigns an output value to a field device through a specified I/O channel. The block supports mode control, signal status calculation, and simulation. Figure 4‐7 illustrates the internal components of the AO function block, and table 4‐25 lists the definitions of the block parameters.
  • Page 116: Controller

    Instruction Manual Detailed Setup—AO Function Block July 2013 D103412X012 Figure 4‐7. Analog Output Function Block Schematic RCAS OUT RCAS IN BKCAL OUT READ BACK SP RATE DN SP RATE UP Operator Setpoint Convert and Status HI/LO Rate Calculation CAS IN Limit Limit SP WRK SP LOW LIM PV SCALE SP HI LIM IO OPTS MODE Shed Mode Access Access...
  • Page 117 Instruction Manual Detailed Setup—AO Function Block D103412X012 July 2013 D Out of Service (OOS)—The block is not processed. The output channel is maintained at the last value and the status of OUT [9] is set to Bad: Out of Service. The BLOCK_ERR [6] attribute shows Out of Service. D Initialization Manual (Iman)—The path to the output hardware is broken and the AO block output will remain at the last position.
  • Page 118 Instruction Manual Detailed Setup—AO Function Block July 2013 D103412X012 For any shed with no return option, the target mode changes as determined by the option. Therefore, there is no attempt to restore the connection following failure. The behavior on change to the remote cascade target mode is identical to that for Shed With Return Options.
  • Page 119 Instruction Manual Detailed Setup—AO Function Block D103412X012 July 2013 To select the manner of processing the SP and the channel output value configure the setpoint limiting options, the tracking options, and the conversion and status calculations. Output Block PV Status The Output Block PV Status is determined by the value of the PlantWeb Alerts Set PV Status parameter in the transducer block (PWA_SET_STATUS [97]), the Transducer Block mode, and enabled Active PlantWeb alarms.
  • Page 120 Instruction Manual Detailed Setup—AO Function Block July 2013 D103412X012 Figure 4‐8. Analog Output Function Block Timing Diagram CAS_IN, 2 1 macrocycle SP RATE DN 1 macrocycle SP RATE UP TRANSDUCER BLOCK TRAVEL TARGET 1 second 1 second 1 second 1 second B2718‐1 Time Action On Fault Detection To define the action you wish the valve to take when the block is in CAS mode, and the CAS_IN [17] input detects a communication failure, or is commanded to go to fault state by the upstream block or the resource block, configure the following parameters:...
  • Page 121 Instruction Manual Detailed Setup—AO Function Block D103412X012 July 2013 Use Fault State value on Restart—Use the value of FSTATE_VAL [24] for SP [8] when power is restored or if the device is restarted, otherwise use the last value saved in non‐volatile memory. This does not act like Fault State, it only uses the value of FSTATE_VAL [24].
  • Page 122 Instruction Manual Detailed Setup—AO Function Block July 2013 D103412X012 Table 4‐24. BLOCK_ERR Conditions Condition Number Condition Name and Description Other (N/A) Block Configuration Error ‐ CHANNEL and SHED_OPT set to 0 Link Configuration Error (N/A) Simulate active ‐ Simulation is enabled and the block is using a simulated value in its execution. Local Override ‐...
  • Page 123 Instruction Manual Detailed Setup—AO Function Block D103412X012 July 2013 Table 4‐25. Analog Output Function Block Parameter Definitions (Continued) Label Index RO / Block Initial Range Description PARAMETER_NAME Number Mode Value Block Mode MODE_BLK OOS until Data Type: DS‐69 block is Valid Bits: 7: OOS, 6: IMAN, 5: LO, 4: MAN, 3: AUTO, TARGET AUTO...
  • Page 124 Instruction Manual Detailed Setup—AO Function Block July 2013 D103412X012 Table 4‐25. Analog Output Function Block Parameter Definitions (Continued) Label Index RO / Block Initial Range Description PARAMETER_NAME Number Mode Value Grant Deny Data Type: DS‐70 GRANT_DENY Options for controlling access of host computers and local control panels to operating, tuning, and 0: Program GRANT...
  • Page 125 Instruction Manual Detailed Setup—AO Function Block D103412X012 July 2013 Table 4‐25. Analog Output Function Block Parameter Definitions (Continued) Label Index RO / Block Initial Range Description PARAMETER_NAME Number Mode Value Data Type: Float Fault State Value PV Scale +/- 10% Preset value to use if I/O_OPTS Fault State to Value FSTATE_VAL or Use Fault State Value on Restart is set.
  • Page 126 Instruction Manual Detailed Setup—AO Function Block July 2013 D103412X012 Table 4‐25. Analog Output Function Block Parameter Definitions (Continued) Label Index RO / Block Initial Range Description PARAMETER_NAME Number Mode Value Extended Parameters Data Type: Float StdDev positive float Dynamic Standard Deviation. To support DeltaV Variability STDDEV measurement.
  • Page 127 Instruction Manual Detailed Setup—AO Function Block D103412X012 July 2013 Field Communicator Menu Structure ANALOG OUTPUT FUNCTION BLOCK Quick Config Online Alert Key Characteristics Back Calculation Output: Status Process Value Scale: EU at 100% Static Revision Back Calculation Output: Value Process Value Scale: EU at 0% Tag Description Block Error Process Value Scale: Units Index...
  • Page 128: Function Block

    Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 PID Function Block Overview The PID function block (figure 4‐9) combines all of the necessary logic to perform proportional/integral/derivative (PID) control. The block supports mode control, signal scaling and limiting, feedforward control, override tracking, alarm limit detection, and signal status propagation.
  • Page 129 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 α: fixed smoothing factor of 0.1 applied to RATE feedforward control contribution from the feedforward input (FF_VAL) error between setpoint and process variable To further customize the block for use in your application, you can configure filtering, feedforward inputs, tracking inputs, setpoint and output limiting, PID equation structures, and block output action.
  • Page 130 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 Modes The PID function block supports the following modes: D Manual (Man)—The block output (OUT [9]) may be set manually. D Automatic (Auto)—The SP [8] may be set manually and the block algorithm calculates OUT [9]. D Cascade (Cas)—The SP [8] is calculated in another block and is provided to the PID block through the CAS_IN [18] connection.
  • Page 131 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 Shed With No Return Options For any shed with no return option, the target mode changes as determined by the option. Therefore, there is no attempt to restore the connection following failure. The behavior on change to a remote target mode is identical to that for Shed With Return Options.
  • Page 132 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 In Manual mode the output is entered manually by the operator. In Remote Output mode, the output is entered by a host computer. Output Selection and Limiting Output selection is determined by the mode and the set point. In Automatic, Cascade, or Remote Cascade mode, the output is computed by the PID control equation.
  • Page 133 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 D Act On IR—If this option is true, then when IR (Initialization Requested) is received on BKCAL_IN [27], the SP [8] will be adjusted within setpoint limits to provide bumpless transfer when the cascade is closed. If the setpoint required to provide bumpless transfer is outside the setpoint limits, then any difference added to provide bumpless transfer will be removed in the BAL_TIME [25].
  • Page 134 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 Process alarm detection is based on the PV [7] value. You can configure the alarm limits of the following standard alarms: D High (HI_LIM [51]) D High high (HI_HI_LIM [49]) D Low (LO_LIM [53]) D Low low (LO_LO_LIM [55]) Additional process alarm detection is based on the difference between SP [8] and PV [7] values and can be configured via the following parameters:...
  • Page 135 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 Table 4‐31. BLOCK_ERR Conditions Condition Number Condition Name and Description Other (N/A) Block Configuration Error—SHED_OPT or BYPASS set to 0 Link Configuration Error (N/A) Simulate Active (N/A) Local Override—The actual mode is LO and Track Enable is set. Device Fault State Set (N/A) Device Needs Maintenance Soon (N/A) Input failure/process variable has Bad status—The parameter linked to IN is indicating a Bad status.
  • Page 136 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Data Type: Bit String Defined Bits 0 = inactive 1: Block Configuration Error 1 = active Block Error 4: Local Override...
  • Page 137 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Data Type: Enum Used to override the calculation of the block. Bypass 1=Off 0=undefined...
  • Page 138 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode BAD: NoCom: Data Type: DS‐65 Status Remote Out Input NoVal: Target output and status that is provided by a ROUT_IN const...
  • Page 139 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Update Event UPDATE_EVT 0=Undefined UNACKNOWLEDGED 43.1 1=Acknowledged Unacknowledged Data Type: DS‐73 0=Undefined This alert is generated by any changes to the static UPDATE_STATE...
  • Page 140 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Data Type: Float Low Low Limit The setting for the alarm limit used to detect the PV_SCALE, or -INF -INF LO_LO_LIM...
  • Page 141 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Low Low Alarm LO_LO_ALM 0=Undefined UNACKNOWLEDGED 63.1 1=Acknowledged 0=undefined Data Type: DS‐71 Unacknowledged The LO LO alarm data, which includes a value of the 0=Undefined...
  • Page 142 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode 0=PID terms on error 1=PI terms on error, D term on PV 2=I terms on error, PD term on PV...
  • Page 143 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 Table 4‐32. PID Function Block System Parameters Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode T Ipgain Data Type: Float T_IPGAIN Integrated process gain. T Ugain Data Type: Float T_UGAIN Ultimate gain.
  • Page 144 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 Table 4‐36. PID Function Block, View 4.1 Table 4‐35. PID Function Block, View 3 Index Number Parameter Index Number Parameter ST_REV ST_REV STRATEGY MODE_BLK.TARGET_MODE ALERT_KEY MODE_BLK.ACTUAL_MODE CONTROL_OPTS MODE_BLK.PERMITTED_MODE STATUS_OPTS MODE_BLK.NORMAL_MODE PV_FTIME BLOCK_ERR SP_RATE_DN SP_RATE_UP...
  • Page 145 Instruction Manual Detailed Setup—PID Function Block D103412X012 July 2013 Field Communicator Menu Structure PID FUNCTION BLOCK Advanced Config Online Quick Config Back Calculation Hysteresis Back Calculation Input: Status Alert Key Feed Forward Gain Back Calculation Intput: Value Control Options Feed Forward Scale: EU at 100% Back Calculation Output: Status Deviation High Limit Feed Forward Scale: EU at 0%...
  • Page 146 Instruction Manual Detailed Setup—PID Function Block July 2013 D103412X012 All (continued) All (continued) PID FUNCTION BLOCK cont. Other Characteristics: Block Tag Updated Event: Unacknowledged Cap StdDev Other (continued) Static Revision Update Event: Update State T Request Tag Description Update Event: Time Stamp T State Error Tag Description...
  • Page 147: Input Selector Function Block

    Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 Input Selector Function Block Overview The Input Selector (ISEL) function block (figure 4‐12) can be used to select the first good, maximum, minimum, average, or hot backup from as many as eight input values and place it at the output. The block supports signal status propagation.
  • Page 148 Instruction Manual Detailed Setup—ISEL Function Block July 2013 D103412X012 D The Input Selector block Target mode is Auto, OP_SELECT [22] is not being used, and SELECT_TYPE [19] is 0. In this case, the BLOCK_ERR [6] parameter shows a Block Configuration Error. The Input Selector block Actual mode will be Manual if all of the above is not true and the Target mode is Manual.
  • Page 149 Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 When the block is in the Manual mode the status and substatus of OUT [7] and SELECTED [21] will be as follows: D Substatus will be non‐specific and the limit will be constant. D Quality of OUT [7] and SELECTED [21] will be Uncertain if STATUS_OPTS [10] is “Uncertain if in Manual mode.”...
  • Page 150 Instruction Manual Detailed Setup—ISEL Function Block July 2013 D103412X012 Figure 4‐14. Input Selector Block Limit Propagation START Propagate OP_SELECT selected input equal to zero? limit status All inputs with SELECT_TYPE same limit Average? status? Propagate Not Limited Propagate that All inputs with limit status More than 1 SELECT_TYPE...
  • Page 151 Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 Figure 4‐15. Input Selector Block Substatus Propagation START Propagate Bad, MODE_BLK Out of Service OOS? STATUS_OPTS Un­ Propagate MODE_BLK certain if Man Uncertain MAN? Mode? Propagate Good Noncascade MODE_BLK must be Auto Propagate Bad, OP_SELECT Nonspecific...
  • Page 152 Instruction Manual Detailed Setup—ISEL Function Block July 2013 D103412X012 STATUS_OPTS Supported In the STATUS_OPTS [10] parameter, you can select from the following options to control the status handling: D Use Uncertain as Good—sets the OUT [7] status to Good when the selected input status is Uncertain. D Uncertain if in Manual mode: sets the OUT [7] status to Uncertain when the mode is Manual.
  • Page 153 Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 IN_1 through IN_8 and DISABLE_1 through DISABLE_8 are non‐volatile type parameters so if they are Linked they will automatically have Bad status until connections are re‐established. If they are not Linked, they will be restored with the previous value from NVM across device restarts.
  • Page 154 Instruction Manual Detailed Setup—ISEL Function Block July 2013 D103412X012 Alarms are grouped into five levels of priority, as shown in table 4‐38. Table 4‐38. ISEL Function Block Alarm Priorities Priority Number Priority Description The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected. An alarm condition with a priority of 1 can be recognized by the system.
  • Page 155 Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 Table 4‐40. Input Selector Function Block Parameter Definitions Label Index Block Initial RO / RW Range Description PARAMETER_NAME Number Mode Value Data Type: Unsigned16 The revision level of the static data associated with the Static Revision 0 to 65535 function block.
  • Page 156 Instruction Manual Detailed Setup—ISEL Function Block July 2013 D103412X012 Table 4‐40. Input Selector Function Block Parameter Definitions (Continued) Label Index Block Initial RO / RW Range Description PARAMETER_NAME Number Mode Value Status Input 3 Data Type: DS‐65 constant IN_3 The block input value and status. Value Status Input 4...
  • Page 157 Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 Table 4‐40. Input Selector Function Block Parameter Definitions (Continued) Label Index Block Initial RO / RW Range Description PARAMETER_NAME Number Mode Value Update Event UPDATE_EVT 0=Undefined UNACKNOWLEDGED 23.1 1=Acknowledged 2=Unacknowledged 0=Undefined Data Type: DS‐73 1=Update Reported This alert is generated by any change to the static data.
  • Page 158 Instruction Manual Detailed Setup—ISEL Function Block July 2013 D103412X012 Table 4‐40. Input Selector Function Block Parameter Definitions (Continued) Label Index Block Initial RO / RW Range Description PARAMETER_NAME Number Mode Value Value Data Type: DS‐66 constant Disable Analog Input 7 Enable/Disable for Input_7, If parameter is TRUE then DISABLE_7 input is disabled.
  • Page 159 Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 Table 4‐40. Input Selector Function Block Parameter Definitions (Continued) Label Index Block Initial RO / RW Range Description PARAMETER_NAME Number Mode Value High Alarm HI_ALM 0=Undefined UNACKNOWLEDGED 46.1 1=Acknowledged Unacknowledged 0=Undefined Data Type: DS‐71 1=Clear reported The high alarm data, which includes a value of the...
  • Page 160 Instruction Manual Detailed Setup—ISEL Function Block July 2013 D103412X012 Table 4‐41. ISEL Function Block, View 1 Table 4‐43. ISEL Function Block, View 3 Index Number Parameter Index Number Parameter ST_REV ST_REV MODE_BLK.TARGET_MODE MODE_BLK.TARGET_MODE MODE_BLK.ACTUAL_MODE MODE_BLK.ACTUAL_MODE MODE_BLK.PERMITTED_MODE MODE_BLK.PERMITTED_MODE MODE_BLK.NORMAL_MODE MODE_BLK.NORMAL_MODE BLOCK_ERR BLOCK_ERR IN_1 IN_1...
  • Page 161 Instruction Manual Detailed Setup—ISEL Function Block D103412X012 July 2013 Field Communicator Menu Structure INPUT SELECTOR FUNCTION BLOCK Quick Config Online All continued Alert Key Alarm Summary: Current Block Error Characteristics Min Good Alarm Summary: Unacknowledged Disable Analog Input 1: Status Static Revision Output Range: EU at 100% Alarm Summary: Unreported...
  • Page 162: Output Splitter Function Block

    Instruction Manual Detailed Setup—OS Function Block July 2013 D103412X012 Output Splitter Function Block Overview The Output Splitter (OS) block (figure 4‐16) provides the capability to drive two control outputs from a single input. Each output is a linear function of some portion of the input. Back calculation support is provided using the same linear function in reverse.
  • Page 163 Instruction Manual Detailed Setup—OS Function Block D103412X012 July 2013 Figure 4‐17. Output Splitter Function Block Schematic IN_ARRAY OUT_ARRAY LOCKVAL RCAS_IN CAS_IN Auto BKCAL_IN_1 RCAS_OUT BKCAL_IN_2 CAS_OUT Figure 4‐18. Output Splitter Function Block Schematic Diagram Setpoint SP_WRK Setpoint " Rate Limiting "...
  • Page 164 Instruction Manual Detailed Setup—OS Function Block July 2013 D103412X012 D Out of Service (OOS)—The block is not processed. FIELD_VAL and PV are not updated and the OUT status is set to Bad: Out of Service. The BLOCK_ERR parameter shows Out of Service. In this mode, you can make changes to all configured parameters.
  • Page 165 Instruction Manual Detailed Setup—OS Function Block D103412X012 July 2013 Limit Handling The splitter function block is designed to combine the limit information from the two downstream blocks into limits for the upstream block. The general principle is to allow the upstream block to continue control for as long as possible. The upstream block is high‐limited (BKCAL_OUT of the Splitter block has high‐limited status) when: D Both downstream blocks are high‐limited (both BKCAL_INS of the Splitter block have high‐limited status) D One downstream block is high‐limited, the associated output slope is positive, and the other block has Bad status or...
  • Page 166 Instruction Manual Detailed Setup—OS Function Block July 2013 D103412X012 blocks may effect the useful range of a line. Units of percent are used in the examples because the common application of this block is to valves, but any units may be used to suit the application. Figure 4‐19.
  • Page 167 Instruction Manual Detailed Setup—OS Function Block D103412X012 July 2013 to OUT_2, or goes to Y . If LOCKVAL is true, OUT_1 remains at its ending value when X is greater than X . If LOCKVAL is false, then OUT_1 goes to Y when X is greater than X Figure 4‐20.
  • Page 168 Instruction Manual Detailed Setup—OS Function Block July 2013 D103412X012 CAS_IN of the Splitter receives the OUT of PID1. BKCAL_IN of PID1 receives BKCAL_OUT of the Splitter. CAS_IN of the AO receives OUT_1 of the Splitter and PID2 receives OUT_2 of the Splitter. BKCAL_IN_1 of the Splitter receives BKCAL_OUT of the AO and BKCAL_IN_2 of the Splitter receives BKCAL_OUT of PID2.
  • Page 169 Instruction Manual Detailed Setup—OS Function Block D103412X012 July 2013 drop the good downstream block out of Cas mode for one evaluation cycle and then restore Cas mode. This initializes the upstream controller to the remaining good region of control. OS Function Block Parameter List (table 4‐48) D Read/Write Capability: RO - Read Only, RW - Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter...
  • Page 170 Instruction Manual Detailed Setup—OS Function Block July 2013 D103412X012 Table 4‐48. Output Splitter Function Block Parameter Definitions (Continued) Label Index RO / Block Initial Range Description PARAMETER_NAME Number Mode Value EU at 100% Data Type: DS‐68 Output 2 Range EU at 0 % The high and low scale values, engineering units code, and OUT_2_RANGE Unit Index...
  • Page 171 Instruction Manual Detailed Setup—OS Function Block D103412X012 July 2013 Table 4‐48. Output Splitter Function Block Parameter Definitions (Continued) Label Index RO / Block Initial Range Description PARAMETER_NAME Number Mode Value Block Alarm BLOCK_ALM 0: Undefined 1: Acknowledged UNACKNOWLEDGED 24.1 2: Unacknowledged 0: Undefined Data Type: DS‐72 1: Clear reported...
  • Page 172 Instruction Manual Detailed Setup—OS Function Block July 2013 D103412X012 Field Communicator Menu Structure OUTPUT SPLITTER FUNCTION BLOCK Characteristics Static Revision Tag Description Strategy Alert Key Block Mode: Target Block Mode: Actual Block Mode: Permitted Block Mode: Normal Block Error Setpoint: Status Setpoint: Value Output 1: Status Output 1: Value...
  • Page 173: Analog Input Function Block

    Instruction Manual Detailed Setup—AI Function Block D103412X012 July 2013 Analog Input Function Block Overview The Analog Input (AI) function block (figure 4‐23) processes field device measurements and makes them available to other function blocks. The output value from the AI block is in engineering units and contains a status indicating the quality of the measurement.
  • Page 174 Instruction Manual Detailed Setup—AI Function Block July 2013 D103412X012 Figure 4‐24. Analog Input Function Block Schematic ANALOG MEASUREMENT ALARM_TYPE ACCESS HI_HI_LIM ANALOG HI_LIM MEAS. ALARM LO_LO_LIM DETECTION LO_LIM OUT_D CHANNEL ALARM_HYS LOW_CUT CUTOFF FILTER CONVERT STATUS CALC. SIMULATE L_TYPE PV_FTIME MODE FIELD_VAL IO_OPTS...
  • Page 175 Instruction Manual Detailed Setup—AI Function Block D103412X012 July 2013 Table 4‐54. Channel Selections for the Analog Input Function Block Channel Parameter Block Index Number XD_SCALE Units TRAVEL_TARGET % (1342) FINAL_POSITION_VALUE % (1342) TRAVEL % (1342) SUPPLY_PRESS psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145) PRESSURE_A psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145) PRESSURE_B...
  • Page 176 Instruction Manual Detailed Setup—AI Function Block July 2013 D103412X012 Filtering The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid changes in input. You can adjust the filter time constant (in seconds) using the PV_FTIME [18] parameter. Set the filter time constant to zero to disable the filter feature.
  • Page 177 Instruction Manual Detailed Setup—AI Function Block D103412X012 July 2013 When the converted input value is below the limit specified by the LOW_CUT [17] parameter, a value of zero is used for the converted value (PV [7]). This option is useful to eliminate false readings when the differential pressure measurement is close to zero.
  • Page 178 Instruction Manual Detailed Setup—AI Function Block July 2013 D103412X012 Troubleshooting Refer to table 4‐56 to troubleshoot any problem that you encounter. Table 4‐56. Troubleshooting Symptom Possible Causes Corrective Action Mode will not leave OOS Target mode is not set Set target mode to something other than OOS BLOCK_ERR [6] will show the configuration error bit set.
  • Page 179 Instruction Manual Detailed Setup—AI Function Block D103412X012 July 2013 Table 4‐57. Analog Input Block Parameter Definitions Label Index RO / Write Block Initial Range Description PARAMETER_NAME Number Mode Value Data Type: Unsigned16 The revision level of the static data associated with Static Revision the function block.
  • Page 180 Instruction Manual Detailed Setup—AI Function Block July 2013 D103412X012 Table 4‐57. Analog Input Block Parameter Definitions (Continued) Label Index RO / Write Block Initial Range Description PARAMETER_NAME Number Mode Value Grant Deny Data Type: DS‐70 GRANT_DENY Options for controlling access of host computer and Valid Bits local control panels to operating, tuning, and alarm GRANT...
  • Page 181 Instruction Manual Detailed Setup—AI Function Block D103412X012 July 2013 Table 4‐57. Analog Input Block Parameter Definitions (Continued) Label Index RO / Write Block Initial Range Description PARAMETER_NAME Number Mode Value Alarm Summary Data Type: DS‐74 Current alert status, ALARM_SUM unacknowledged states, unreported states, and disabled states of the alarms associated with the 0: Discrete alarm CURRENT...
  • Page 182 Instruction Manual Detailed Setup—AI Function Block July 2013 D103412X012 Table 4‐57. Analog Input Block Parameter Definitions (Continued) Label Index RO / Write Block Initial Range Description PARAMETER_NAME Number Mode Value Low Low Alarm LO_LO_ALM UNACKNOWLEDGED 36.1 Data Type: DS‐71 ALARM_STATE 36.2 The status of the lo lo alarm and its associated time stamp.
  • Page 183 Instruction Manual Detailed Setup—AI Function Block D103412X012 July 2013 Table 4‐60. AI Function Block, View 3 Table 4‐61. AI Function Block, View 4 Index Number Parameter Index Number Parameter ST_REV ST_REV MODE_BLK.TARGET_MODE STRATEGY MODE_BLK.ACTUAL_MODE ALERT_KEY MODE_BLK.PERMITTED_MODE IO_OPTS MODE_BLK.NORMAL_MODE STATUS_OPTS BLOCK_ERR CHANNEL L_TYPE LOW_CUT...
  • Page 184 Instruction Manual Detailed Setup—AI Function Block D103412X012 July 2013 Field Communicator Menu Structure ANALOG INPUT FUNCTION BLOCK Quick Config Online All (continued) AI Channel Block Error Characteristics Alarm Hysteresis Linearization Type Field Value: Status Static Revision High High Priority Transducer Scale: EU at 100% Field Value: Value Tag Description High High Limit...
  • Page 185: Mulitple Analog Input Function Block

    Instruction Manual Detailed Setup—MAI Function Block D103412X012 July 2013 Multiple Analog Input Function Block Overview The Multiple Analog Input (MAI) function block (figure 4‐26) has the ability to process up to eight field device measurements and make them available to other function blocks. The output values from the MAI block are in engineering units and contain a status indicating the quality of the measurement.
  • Page 186 Instruction Manual Detailed Setup—MAI Function Block July 2013 D103412X012 OUT_X status will be Bad if the transducer detects a problem with sensor associated with the channel. Application Information The intended use is for applications where it is necessary to convey DVC6200f measurements from a function. The configuration of the MAI function block and its associated output channels depends on the specific application.
  • Page 187 Instruction Manual Detailed Setup—MAI Function Block D103412X012 July 2013 MAI Function Block Parameter List (table 4‐64) D Read/Write Capability: RO - Read Only, RW - Read Write D Mode: The block mode(s) required to write to the parameter D Double indentation and shaded Index Number indicates sub‐parameter Table 4‐64.
  • Page 188 Instruction Manual Detailed Setup—MAI Function Block July 2013 D103412X012 Table 4‐64. MAI Function Block Parameter Definitions (Continued) Label Index RO / Mode Range Initial Value Description Parameter Name Number Output 1 Channel assigned by Data Type: DS‐65 TB.FINAL_VALUE OUT_1 TB.MAI_CHANNEL_MAP The block output value and status.
  • Page 189 Instruction Manual Detailed Setup—MAI Function Block D103412X012 July 2013 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information.
  • Page 190 Instruction Manual Detailed Setup—MAI Function Block July 2013 D103412X012 Field Communicator Menu Structure MULTIPLE ANALOG INPUT FUNCTION BLOCK Quick Config Online MAI Channel Block Error Characteristics Block Mode: Target Static Revision Block Mode: Actual Tag Description Common Config Block Mode: Permitted Strategy Block Mode: Normal Alert Key...
  • Page 191: Discrete Output Function Block

    Instruction Manual Detailed Setup—DO Function Block D103412X012 July 2013 Discrete Output Function Block Overview The Discrete Output (DO) function block (figure 4‐27) processes a discrete set point and outputs it to the specified I/O channel to produce an output signal. The DVC6200f digital valve controller discrete output block provides both normal open/closed control and the ability to position the valve in 5% increments for coarse throttling applications.
  • Page 192 Instruction Manual Detailed Setup—DO Function Block July 2013 D103412X012 Figure 4‐28. Discrete Output Function Block Schematic RCAS_OUT_D RCAS_IN_D BKCAL_OUT_D PV_D SP_D CONVERT AND STATUS CAS_IN_D OUT_D CALCULATION READBACK_D IO_OPTS MODE SIMULATE_D SHED MODE CHANNEL TRANSDUCER TRANSDUCER BLOCK FEEDBACK BLOCK When setting up the DO block, CHANNEL [18] must be set to 22, and SHED_OPT [23] must be non‐zero. Note Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain out of service and the block cannot be scheduled if the block has not been licensed.
  • Page 193 Instruction Manual Detailed Setup—DO Function Block D103412X012 July 2013 D Cascade (Cas)—The block uses a set point supplied by another function block. Note The transducer block must be in Auto for the mode to go to AUTO, CAS or MAN. D RemoteCascade (RCas)—The block uses a set point supplied by a host computer. D Out of Service (OOS)—The block is not processed and the output is not transferred to I/O.
  • Page 194 Instruction Manual Detailed Setup—DO Function Block July 2013 D103412X012 Auto—On failure of a remote cascade connection, the block sets the target mode to Auto, if permitted. Man—On failure of remote cascade connection, the block sets the target mode to Man, if permitted. The user may configure SHED_OPT [23] so that it calls for a target mode that is not permitted.
  • Page 195 Instruction Manual Detailed Setup—DO Function Block D103412X012 July 2013 Table 4‐70. Valve Set Point for Discrete State Discrete State Valve Set Point with IO_OPTS Invert = 0 Valve Set Point with IO_OPTS Invert = 1 Closed Open Open Closed Closed Closed Closed Closed...
  • Page 196 Instruction Manual Detailed Setup—DO Function Block July 2013 D103412X012 Block Errors Table 4‐71 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the DO block and are provided only for your reference. Table 4‐71. BLOCK_ERR Conditions Condition Number Condition Name and Description Other (N/A)
  • Page 197 Instruction Manual Detailed Setup—DO Function Block D103412X012 July 2013 Note When simulate is active, the output block no longer writes values to the transducer block. If the Output Blk Timeout period is exceeded, the transducer block may move the valve to the Zero Power Condition depending on the configuration of the Output Block Timeout Alert.
  • Page 198 Instruction Manual Detailed Setup—DO Function Block July 2013 D103412X012 Table 4‐72. Discrete Output Function Block Parameter Definitions (Continued) Label Index RO / Mode Range Initial Value Description PARAMETER_NAME Number Block Mode MODE_BLK Data Type: DS‐69 OOS until Valid Bits: 7: OOS, 5: LO, 4: MAN, 3: AUTO block is TARGET 2: CAS, 1: RCAS...
  • Page 199 Instruction Manual Detailed Setup—DO Function Block D103412X012 July 2013 Table 4‐72. Discrete Output Function Block Parameter Definitions (Continued) Label Index RO / Mode Range Initial Value Description PARAMETER_NAME Number Valid Bits 0: Invert 1: SP tracks PV in Man 3: SP tracks PV in LO Data Type: Bit String 4: SP Track retained 0=Disable...
  • Page 200 Instruction Manual Detailed Setup—DO Function Block July 2013 D103412X012 Table 4‐72. Discrete Output Function Block Parameter Definitions (Continued) Label Index RO / Mode Range Initial Value Description PARAMETER_NAME Number 0=Uninitialized 1=Normal Shed, Normal Return 2=Normal Shed, No Return 3=Shed to Auto, normal return 4=Shed to Auto, no Data Type: Unsigned8...
  • Page 201 Instruction Manual Detailed Setup—DO Function Block D103412X012 July 2013 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information.
  • Page 202 Instruction Manual Detailed Setup—DO Function Block July 2013 D103412X012 Field Communicator Menu Structure DISCRETE OUTPUT FUNCTION BLOCK Quick Config Online Alert Key Back Calculation Output Discrete: Status Characteristics Process Value Discrete: Status Back Calculation Output Discrete: Value Static Revision Process Value Discrete: Value Block Error Tag Description Setpoint Discrete: Status...
  • Page 203: Discrete Input Function Block

    Instruction Manual Detailed Setup—DI Function Block D103412X012 July 2013 Discrete Input Function Block Overview The Discrete Input (DI) function block (figure 4‐29) processes a single discrete input from a field device and makes it available to other function blocks. You can configure inversion and alarm detection on the input value. In the DVC6200f digital valve controller, the discrete input function block can provide limit switch functionality and valve position proximity detection.
  • Page 204 Instruction Manual Detailed Setup—DI Function Block July 2013 D103412X012 Modes The Discrete Input function block supports the following modes: D Manual (Man)—The block output (OUT_D [8]) is disconnected from the field and set manually. D Automatic (Auto)—The block algorithm determines output. D Out of Service (OOS)—The block is not processed. The OUT_D [8] status is set to Bad: Out of Service. The BLOCK_ERR [6] parameter shows Out of Service.
  • Page 205 Instruction Manual Detailed Setup—DI Function Block D103412X012 July 2013 Table 4‐77. Channel Selection for the Discrete Input Function Block Selection Transducer Block Parameter Transducer Block Index Number Bit Number TRAVEL_D INST_ALERTS_ACTIVE:PROX_ACTIVE 74.5 0: Travel Open INST_ALERTS_ACTIVE:PROX_ACTIVE 74.5 1: Travel Closed INST_ALERTS_ACTIVE:TRAVEL_ACTIVE 74.4 2: Travel Limit Lo Lo...
  • Page 206 Instruction Manual Detailed Setup—DI Function Block July 2013 D103412X012 the detected position. Figure 4‐31 illustrates the operation of the proximity detection function. Travel Alert Point refers to Travel Lo Alert Point, Travel Hi Alert Point, Travel Lo Lo Alert Point, and Travel Hi Hi Alert Point in table 4‐79. Travel Alert Deadband refers to Travel Lo Alert Deadband, Travel Hi Alert Deadband, Travel Lo Lo Alert Deadband, and Travel Hi Hi Alert Deadband in table 4‐79.
  • Page 207 Instruction Manual Detailed Setup—DI Function Block D103412X012 July 2013 Alarm Detection To select the state that initiates an input alarm, and to set discrete alarm substatus in the output, configure the DISC_LIM [23] parameter. You can enter any value between 0 and 255. A value of 255 disables the alarm. When OUT_D [8] matches the DISC_LIM [23] state, the discrete value of an alarm is set.
  • Page 208 Instruction Manual Detailed Setup—DI Function Block July 2013 D103412X012 To use simulate, first install the simulate jumper in the terminal box, then set Simulate_D enable/disable to enabled, then enter the desired values for Simulate Value and Status. When SIMULATE_D [9] is enabled, the Simulate Active bit of the BLOCK_ERR [6] parameter is set (refer to the Block Errors description).
  • Page 209 Instruction Manual Detailed Setup—DI Function Block D103412X012 July 2013 Table 4‐81. Discrete Input Function Block Parameter Definitions Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Data Type: Unsigned16 The revision level of the static data associated Static Revision 0 to 65535 with the function block.
  • Page 210 Instruction Manual Detailed Setup—DI Function Block July 2013 D103412X012 Table 4‐81. Discrete Input Function Block Parameter Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Data Type: DS‐70 Grant Deny Options for controlling access of host GRANT_DENY computers and local control panels to operating, tuning, and alarm parameters of...
  • Page 211 Instruction Manual Detailed Setup—DI Function Block D103412X012 July 2013 Table 4‐81. Discrete Input Function Block Parameter Definitions (Continued) Label Index RO / Block Range Initial Value Description PARAMETER_NAME Number Mode Block Alarm Dynamic BLOCK_ALM Data Type: DS‐72 0=Undefined The block alarm is used for all configuration, UNACKNOWLEDGED 19.1 1=Acknowledged...
  • Page 212 Instruction Manual Detailed Setup—DI Function Block July 2013 D103412X012 View Lists View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains static parameters with configuration and maintenance information.
  • Page 213 Instruction Manual Detailed Setup—DI Function Block D103412X012 July 2013 Field Communicator Menu Structure DISCRETE INPUT FUNCTION BLOCK Quick Config Online Alert Key Block Error Characteristics Process Value Discrete: Status Field Value Discrete: Status Static Revision Process Value Discrete: Value Field Value Discrete: Value Tag Description Block Mode: Target Strategy...
  • Page 214 Instruction Manual Detailed Setup—DI Function Block July 2013 D103412X012...
  • Page 215: Section 5 Calibration

    Instruction Manual Calibration D103412X012 July 2013 Section 5 Calibration 5-5- Calibration Overview When a DVC6200f digital valve controller is ordered as part of a control valve assembly, the factory mounts the digital valve controller on the actuator and connects the necessary tubing, then sets up and calibrates the controller. For digital valve controllers that are ordered separately, recalibration of the pressure sensors generally is unnecessary.
  • Page 216: Auto

    Instruction Manual Calibration July 2013 D103412X012 If a double‐acting relay is used, you will be prompted to run the relay adjustment when auto or manual calibration is selected. Select Yes to adjust the relay, select No to proceed with calibration. For additional information, refer to Relay Adjustment in this section.
  • Page 217: Relay

    Instruction Manual Calibration D103412X012 July 2013 Relay Field Communicator TB > Configure/Setup > Calibration > Relay Follow the prompts on the Field Communicator display to check relay adjustment. Replace the digital valve controller cover when finished. Note Relay B and C are not user‐adjustable. Double‐Acting Relay The double‐acting relay is designated by “Relay A”...
  • Page 218: Supply Pressure Sensor

    Instruction Manual Calibration July 2013 D103412X012 If the low bleed relay option has been ordered stabilization may take approximately two minutes longer than the standard relay. Relay A may also be adjusted for use in single‐acting‐ direct applications. Rotate the adjustment disc as shown in figure 5‐1 for single‐acting direct operation.
  • Page 219: Pressure A Or B Sensor

    Instruction Manual Calibration D103412X012 July 2013 2. The following message appears: Use the Increase and Decrease selections until the displayed pressure matches the instrument supply pressure. Press OK when you have read this message. 3. The value of the pressure appears on the display. 4.
  • Page 220 Instruction Manual Calibration July 2013 D103412X012 5. The instrument sets the output pressure to full supply. The following message appears. Use the Increase and Decrease selections until the displayed pressure matches the output x pressure. Press OK when you have read the message. 6.
  • Page 221: Section 6 Viewing Device Variables And Diagnostics

    Instruction Manual Viewing Device Variables and Diagnostics D103412X012 July 2013 Section 6 Viewing Device Variables and Diagnostics6-6- View Lists View Lists allow the values of a set of parameters to be accessed at the same time. View lists are available for the resource and transducer blocks, and the function blocks.
  • Page 222: Device Diagnostics

    Instruction Manual Viewing Device Variables and Diagnostics July 2013 D103412X012 Device Diagnostics Resource Block Error (RB > Device Diagnostics > Resource Block Error) RB > Device Diagnostics > Resource Block Error Field Communicator Block Error (BLOCK_ERR [6]) indicates an error status associated with hardware or software for the resource block. Table 6‐1 lists conditions reported in the BLOCK_ERR [6] parameter.
  • Page 223 Instruction Manual Viewing Device Variables and Diagnostics D103412X012 July 2013 Block Alarm RB > Device Diagnostics > Block Alarm Field Communicator The Block Alarm (BLOCK_ALM [36]) is used for all configuration, hardware, connection failure or system problems in the block. D Block Alarm: Alarm State Block Alarm: Alarm State (BLOCK_ALM.
  • Page 224: Device Variables

    Instruction Manual Viewing Device Variables and Diagnostics July 2013 D103412X012 There are two different restarts: Restart Processor, and Restart with Defaults: When selecting either of these options, Restart informs you of the consequences of this action and asks if you want to continue.
  • Page 225: Transducer Block

    D Manufacturer—Manufacturer Identification (MANUFAC_ID [10]) identifies the manufacturer of the instrument. It is used by the host system to locate the DD file for the device. For Fisher the Manufacturer ID is 0x5100. D Device Type—Device Type (DEV_TYPE [11]) identifies the type of device. It is used by the host system to locate the DD file for the device.
  • Page 226: Device Diagnostics

    Instruction Manual Viewing Device Variables and Diagnostics July 2013 D103412X012 Device Diagnostics Active PlantWeb Alerts TB > Device Diagnostic > Active PlantWeb Alerts Field Communicator To view the active PlantWeb alerts select Active PlantWeb Alerts. Alert Conditions TB > Device Diagnostic > Active Conditions Field Communicator Instrument Alert Conditions, when enabled, detect many operational and performance issues that may be of interest.
  • Page 227 Instruction Manual Viewing Device Variables and Diagnostics D103412X012 July 2013 Blocks Set to Default Blocks Set to Default Alert—This alert is active if the resource block has undergone Restart with Defaults. This will stay active until the transducer block is changed from Out of Service. D Sensor—If a configuration alert is active it will appear under SENSOR ALERTS Travel Sensor Travel Sensor—This alert is active if the Travel Sensor reading is outside the functional range, or the sensor becomes...
  • Page 228 Instruction Manual Viewing Device Variables and Diagnostics July 2013 D103412X012 Travel Closed Travel Closed Alert—This alert is active if the travel is greater than the travel closed alert point. Proximity Proximity Hi Hi Alert—This alert is active if the Travel is within the detection band set by the Travel Hi Hi Alert Point and the Travel Hi Hi Deadband.
  • Page 229 Instruction Manual Viewing Device Variables and Diagnostics D103412X012 July 2013 Travel Sensor Span Error—Indicates that span between the endpoints of travel are not far enough apart. This error is reported during automatic calibration. MLFB Error—Indicates that the Minor Loop Feedback sensor gave a non‐valid value during automatic calibration. Travel Sensor Hi Error—Indicates the travel sensor has reported a travel position that is significantly above the normal operating range, and has failed.
  • Page 230 Instruction Manual Viewing Device Variables and Diagnostics July 2013 D103412X012 Device Record TB > Device Diagnostic > Device Record Field Communicator The following parameters are contained in the Device Record menu of the transducer block. D Maximum Recorded Temperature—Maximum Recorded Temperature (TEMP_MAX [86.1]) shows the maximum temperature the instrument has experienced since installation.
  • Page 231: Device Variables

    Instruction Manual Viewing Device Variables and Diagnostics D103412X012 July 2013 Trend TB > Device Diagnostic > Trend Field Communicator Trend chart of Setpoint (FINAL_VALUE.VALUE [13.2]), Travel (TRAVEL.VALUE [34.2]), and Pressure A (PRESSURE_A.VALUE [36.2]). Device Variables TB > Device Variables Field Communicator All Block Modes Block Mode: Target The Target (TARGET [5.1]) mode is the mode requested by the user or host system.
  • Page 232 Instruction Manual Viewing Device Variables and Diagnostics July 2013 D103412X012 AO Control - Pre‐Characterization D Setpoint Setpoint (FINAL_VALUE.VALUE [13.2]) shows the value of the setpoint in % (percent) of ranged travel or pressure. Setpoint is used for both travel and pressure control. This parameter will be written directly if the transducer block is in MAN mode, or will be written automatically by the AO block if the transducer block is in AUTO mode.
  • Page 233 Instruction Manual Viewing Device Variables and Diagnostics D103412X012 July 2013 Travel/Pressure State Travel/Pressure State (TVL_PRESS.STATE [41.2]) indicates if the instrument is being used for travel control (position control) or as an I/P (pressure control). PD Inside Status PD Inside Status shows the status of Performance Diagnostics. Protection Indicates the status of Protection.
  • Page 234 Instruction Manual Viewing Device Variables and Diagnostics July 2013 D103412X012 Pressures D Supply Supply (SUPPLY_PRESSURE_VALUE [35.2]) shows the value of the supply pressure in psi, bar, kPa, inHg, inH O, or kg/cm D Pressure A Pressure A (PRESSURE_A.VALUE [36.2]) shows the value of Output Pressure A in psi, bar, kPa, inHg, inH O, or kg/cm D Pressure B Pressure B (PRESSURE_B.VALUE [37.2]) shows the value of Output Pressure B in psi, bar, kPa, inHg, inH...
  • Page 235: Section 7 Maintenance And Troubleshooting

    Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 Section 7 Maintenance and Troubleshooting7-7- The DVC6200f digital valve controller enclosure is rated Type 4X and IP66, therefore periodic cleaning of internal components is not required. If the DVC6200f is installed in an area where the exterior surfaces tend to get heavily coated or layered with industrial or atmospheric contaminants, however, it is recommended that the vent (key 52) be periodically inspected to ensure it is fully open.
  • Page 236: Replacing The Magnetic Feedback Assembly

    Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 from fire or explosion if natural gas is used as the supply medium and appropriate preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of the following: ensuring adequate ventilation and the removal of any ignition sources.
  • Page 237: Component Replacement

    Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 Component Replacement When replacing any of the components of the DVC6200f, the maintenance should be performed in an instrument shop whenever possible. Make sure that the electrical wiring and pneumatic tubing is disconnected prior to disassembling the instrument.
  • Page 238: Replacing The Module Base

    Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 Figure 7‐1. Printed Wiring Board Cable Connections TERMINAL MODULE BASE ASSEMBLY PRINTED WIRING BOARD ASSEMBLY HOUSING CABLE CABLE TO TRAVEL SENSOR TO TERMINAL BOX W9924‐1 Replacing the Module Base Refer to figure 8‐2 or 8‐4 for key number locations. Refer to figure 7‐2 for a view of the back of the PWB assembly sub‐module.
  • Page 239: Submodule Maintenance

    Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 1. Ensure the module base seal (key 237) is properly installed in the housing (key 1). Ensure the O‐ring (key 12) is in place on the module base assembly. 2. Connect the terminal box connector to the PWB assembly (key 50). Orientation of the connector is required. 3.
  • Page 240 Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 1. Remove the I/P converter (key 41) and shroud (key 169) as described in the Removing the I/P Converter procedure. 2. Remove the screen (key 231) from the supply port. 3. Install a new screen in the supply port as shown in figure 7‐3. 4.
  • Page 241: Printed Wiring Board (Pwb) Assembly

    Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 Figure 7‐4. I/P Converter SHROUD (KEY 169) I/P CONVERTER SOCKET‐HEAD (KEY 41) SCREWS (4) (KEY 23) BOOTS (KEY 210) W9328 3. Install the I/P converter (key 41) straight into the module base (key 2), taking care that the two electrical leads feed into the guides in the module base.
  • Page 242: Pneumatic Relay

    Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 2. Properly orient the PWB assembly (key 50) as you install it into the module base. The two electrical leads from the I/P converter (key 41) must guide into their receptacles in the PWB assembly and the pressure sensor bosses on the module base must fit into their receptacles in the PWB assembly.
  • Page 243: Gauges, Pipe Plugs Or Tire Valves

    Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 3. Position the relay (with shroud) on the module base. Tighten the four screws, in a crisscross pattern, to a final torque of 2 NSm (20.7 lbfSin). 4. Using the Field Communicator, verify that the value for Relay Type parameter matches the relay type installed. 5.
  • Page 244: Replacing The Terminal Box

    Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 4. Disconnect the terminal box wiring connector from the PWB assembly (key 50). 5. Remove the screw (key 72). Pull the terminal box assembly straight out of the housing. Replacing the Terminal Box Note Inspect all O‐rings for wear and replace as necessary.
  • Page 245: Instrument Troubleshooting

    Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 Instrument Troubleshooting What to Do First When a problem occurs, check the following first: Mounting D Is the feedback linkage connected correctly? See the beginning of this section. Utility Connections D Are pneumatic connections correct? Are there any air leaks? See the Installation section. D Is the air supply pressure sufficient to drive the valve? D Is the digital valve controller correctly connected to the fieldbus? See the Installation section.
  • Page 246 Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 Table 7‐2. Instrument Troubleshooting Symptom Possible Cause Action 1 Instrument will not communicate. 1a No power to device 1a1 Ensure device is connected to the segment (see host system documentation). 1a2 Measure the terminal voltage. Terminal voltage should be between 9 and 32 VDC.
  • Page 247 Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 Table 7‐2. Instrument Troubleshooting (Continued) Symptom Possible Cause Action 4 Function block actual mode does not 4a Resource block actual mode is Out of Service. 4a Change Resource block target mode to Auto (see change with target mode.
  • Page 248 Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 Table 7‐2. Instrument Troubleshooting (Continued) Symptom Possible Cause Action 9c Instrument is in fault state. 9c Set Clear FState to Clear (Refer to Fault State on page 47 of the Detailed Setup / Blocks Section, or host system documentation).
  • Page 249 Instruction Manual Maintenance and Troubleshooting D103412X012 July 2013 Table 7‐2. Instrument Troubleshooting (Continued) Symptom Possible Cause Action 14 Instrument will not calibrate, has 14a Travel sensor failed. 14a Replace the housing (key 1) sluggish performance or oscillates. 14b Travel feedback is out of accepted range 14b Check the mounting.
  • Page 250 Instruction Manual Maintenance and Troubleshooting July 2013 D103412X012 Technical Support Checklist Have the following information available prior to contacting your Emerson Process Management sales office for support. Reference 1. Instrument serial number as read from nameplate _________________________________________ 2. What is the firmware version of the DVC6200f? _________________ 3.
  • Page 251: Section 8 Parts

    Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Process Management should not, under any circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson Process Management may void your warranty, might adversely affect the performance of the instrument, and could cause personal injury and property damage.
  • Page 252: Parts List

    Instruction Manual Parts July 2013 D103412X012 Description Part Number Description  9* Remote Mount Feedback Unit Kit (see figure 8‐5)  [remote housing assembly (key25); hex socket set  screw (key 58); 1/2 NPT pipe plug (key 62); wire retainer, qty 2 Housing (see figure 8‐2 and 8‐4)  (key 131);...
  • Page 253: Module Base

    Parts D103412X012 July 2013 Description Part Number Figure 8‐1. Terminal Box of Natural Gas Certified FIELDVUE DVC6200f Digital Valve Controller WIRING CONNECTOR Relay (see figure 8‐2 and 8‐4) GAS‐BLOCKING PRESS‐FIT ADAPTOR DVC6200f and DVC6205f 24* Relay Assembly, (includes shroud, relay seal, mounting screws)   Standard (nitrile elastomers)
  • Page 254: Pwb Assembly

    Instruction Manual Parts D103412X012 July 2013 Description Description Part Number Feedback Connections Terminal Pressure Gauges, Pipe Plugs, or Box (see figure 8‐4) Tire Valve Assemblies DVC6205f (see figure 8‐3)   4 Terminal Box Cap (1)(4)  34* O‐ring DVC6200f and DVC6205f (1)(4)  36* O‐ring  58 Set Screw, hex socket, SST...
  • Page 255 Instruction Manual Parts D103412X012 July 2013 Figure 8‐2. FIELDVUE DVC6200f Digital Valve Controller Housing Assembly HOUSING B—BACK VIEW HOUSING A—BACK VIEW (USED FOR ALL (USED FOR GX ACTUATOR) ACTUATORS EXCEPT GX) DOUBLE‐ACTING DIRECT‐ACTING REVERSE‐ACTING APPLY LUBRICANT, SEALANT, OR THREAD LOCK...
  • Page 256 Instruction Manual Parts July 2013 D103412X012 Figure 8‐2. FIELDVUE DVC6200f Digital Valve Controller Housing Assembly (continued) SECTION C-C SCALE 2 : 1 SECTION A-A SECTION E-E SCALE 2 : 1 APPLY LUBRICANT, SEALANT, OR THREAD LOCK SECTION F-F SCALE 2 : 1...
  • Page 257 Instruction Manual Parts D103412X012 July 2013 Figure 8‐4. FIELDVUE DVC6205f Base Unit Housing Assembly SECTION B-B SECTION A-A APPLY LUBRICANT, SEALANT, OR THREAD LOCK SECTION H-H APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED GE40181...
  • Page 258 Instruction Manual Parts July 2013 D103412X012 Figure 8‐4. FIELDVUE DVC6205f Base Unit Housing Assembly (continued) SECTION C-C SCALE 2 : 1 SECTION E-E SCALE 2 : 1 DOUBLE‐ACTING SHOWN DOUBLE‐ACTING DIRECT‐ACTING REVERSE‐ACTING APPLY LUBRICANT, SEALANT, OR THREAD LOCK APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED GE40181...
  • Page 259 Instruction Manual Parts D103412X012 July 2013 Figure 8‐4. FIELDVUE DVC6205f Base Unit Housing Assembly (continued) PIPE MOUNTING WALL MOUNTING APPLY LUBRICANT, SEALANT, OR THREAD LOCK APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED GE40181...
  • Page 260 Instruction Manual Parts July 2013 D103412X012 Figure 8‐5. FIELDVUE DVC6215 Remote Feedback Assembly SECTION A-A PARTS NOT SHOWN: 158 APPLY LUBRICANT, SEALANT, OR THREAD LOCK GE46670-B HOUSING A (USED FOR GX ACTUATOR) SECTION A-A PARTS NOT SHOWN: 158 APPLY LUBRICANT, SEALANT, OR THREAD LOCK GE40178-B HOUSING B (USED FOR ALL ACTUATORS EXCEPT GX)
  • Page 261: Appendix A Principle Of Operation

    This sensor is used for the minor loop feedback (MLFB) reading. The master module can be rebuilt by replacing the submodules. See figures A‐1 and A‐2. Figure A‐1. FIELDVUE DVC6200f Digital Valve Controller Block Diagram DIGITAL SETPOINT 9–32 VOLT...
  • Page 262 (output A is not available). With relay C an increasing setpoint will produce an increasing pressure on output A (output B is not available). The output A pressure is used for double‐acting and single‐acting direct applications. The output B pressure is used for double‐acting and single‐acting reverse applications. Figure A‐2. FIELDVUE DVC6200f Digital Valve Controller Assembly HOUSING PNEUMATIC...
  • Page 263: Appendix B Field Communicator Menu Tree

    Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 Appendix B Field Communicator Menu StructureB‐B‐ This section contains the Field Communicator menu trees for the transducer block and the resource block. It also contains Fast Key Sequence tables with coordinates to help locate the function/variable on the appropriate menu tree.
  • Page 264 Instruction Manual Field Communicator Menu Structure July 2013 D103412X012 Transducer Block (TB) Menu Structure Parameter Label Menu Structure A Minus B Device Variables Pressures A Minus B > > > Actual Travel Configure/Setup Detailed Setup Valve and Actuator Valve Actual Travel >...
  • Page 265 Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 Transducer Block (TB) Menu Structure (Continued) Parameter Label Menu Structure Configure/Setup Detailed Setup Response Control Input Characterization > > > > Input Characterization Device Variables Input Characterization > > Integrator Limited Hi Device Diagnostics Status Self Test Status...
  • Page 266 Instruction Manual Field Communicator Menu Structure July 2013 D103412X012 Transducer Block (TB) Menu Structure (Continued) Parameter Label Menu Structure Performance Critical Alert Configure/Setup Detailed Setup Alerts Performance Alerts Performance Critical Alert > > > > > Performance Critical Alert Enable Configure/Setup Detailed Setup Alerts...
  • Page 267 Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 Transducer Block (TB) Menu Structure (Continued) Parameter Label Menu Structure Rated Travel Configure/Setup Detailed Setup Valve and Actuator Valve Rated Travel > > > > > Relay Type Configure/Setup Detailed Setup Instrument Relay Type >...
  • Page 268 Instruction Manual Field Communicator Menu Structure July 2013 D103412X012 Transducer Block (TB) Menu Structure (Continued) Parameter Label Menu Structure Travel Cutoff Lo Configure/Setup Detailed Setup Response Control Travel Pressure Control Travel Cutoff Lo > > > > > Travel Deviation Configure/Setup Detailed Setup Alerts...
  • Page 269 Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 Transducer Block (TB) Menu Structure (Continued) Parameter Label Menu Structure Trim Style 2 Configure/Setup Detailed Setup Valve and Actuator Reference Trim Style 2 > > > > > Unbalanced Area Configure/Setup Detailed Setup Valve and Actuator Trim...
  • Page 270 Instruction Manual Field Communicator Menu Structure July 2013 D103412X012 Travel Tuning TRANSDUCER BLOCK  :Travel Tuning Set DETAILED SETUP  Travel Proportional Gain  Travel Velocity Gain  :Travel MLFB Gain  :Travel Integral Enable Response Control  :Travel Integral Gain  Travel Tuning  :Travel Integral Dead Zone  Pressure Tuning  :Travel Integral Limit Hi  Travel Press Control...
  • Page 271 Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 Drive Current TRANSDUCER BLOCK  Drive Current DETAILED SETUP > ALERTS  :Drive Current Alert (continued on next page)  :Drive Current Alert Enable  :Drive Current Shutdown  :Drive Current Manual Recovery  :Drive Current Alert Point Elect Alerts  :Drive Current Alert Time  Drive Current...
  • Page 272 Instruction Manual Field Communicator Menu Structure July 2013 D103412X012 Travel Deviation Travel Alerts TRANSDUCER BLOCK  Travel Deviation  :Travel Target DETAILED SETUP > ALERTS  :Travel Deviation Alert  :Travel  :Travel Deviation Alert Enable  Travel Deviation  :Travel Deviation Alert Point  Travel Limit  :Travel Deviation Time  Travel Hi/Lo  :Travel Deviation Deadband Travel Open...
  • Page 273 Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 TRANSDUCER BLOCK CALIBRATION Top Level  Configure/Setup Configure/Setup  Device Diagnostics  Basic Setup  Device Variables  Detailed Setup  Calibration Calibration  Auto Calibration  Manual Calibration  Relay   Supply Pressure  Pressure A  Pressure B  TRANSDUCER BLOCK DEVICE DIAGNOSTICS Status Top Level  Self Test Status...
  • Page 274 Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 Resource Block (RB) Menu Structure Parameter Label Menu Structure Alert Key Configure/Setup Alarm Handling Alert Key > > > Block Alarm: Alarm State Device Diagnostics Block Alarm Alarm State > > >...
  • Page 275 Instruction Manual Field Communicator Menu Structure D103412X012 July 2013 Function Write Lock RESOURCE BLOCK Block Options  Write Lock CONFIGURE/SETUP  AO  Write Priority  DO  AI Comm Timeout  DI Configure/Setup  Shed Remote Cascade  PID  Resource Block Mode  Shed Remote Out  IS  Write Lock  OS Top Level  Comm Timeout...
  • Page 276 Instruction Manual Field Communicator Menu Structure July 2013 D103412X012...
  • Page 277: Appendix C Plantweb Alerts

    Instruction Manual PlantWeb Alerts D103412X012 July 2013 Appendix C PlantWeb AlertsC‐C‐ Instrument Alert Conditions Instrument Alert Conditions, when enabled, detect many operational and performance issues that may be of interest. To view these alerts, the user must open the appropriate status screen on a host such as a DeltaV system, ValveLink software or a Field Communicator.
  • Page 278 Instruction Manual PlantWeb Alerts July 2013 D103412X012 Figure C‐1. Alert Handling Set Alert Points Enable Instrument Enable PlantWeb and Deadband in Use Resource and Transducer Alert Condition in Alert in the the Transducer Block Parameters to Configure the Transducer Transducer Block Block Block ALERT...
  • Page 279: Alert Reporting

    Instruction Manual PlantWeb Alerts D103412X012 July 2013 Alert Reporting For PlantWeb alerts to be reported to the operator console, they must pass four tests: d Alerts must be active d Reports must be selected in Feature Select d Alert priority must be greater than 1 d Reporting must not be suppressed for those conditions that caused active alerts.
  • Page 280 Instruction Manual PlantWeb Alerts July 2013 D103412X012 Table C‐2. Setting PlantWeb Alerts PlantWeb Alert Alert Condition Related Parameters What the Alert is Detecting Guidelines for Setting (Group) (Default) (Default) (Default Alert Category) The difference between the Self Test Shutdown (No) Drive Current expected Drive Current and the Drive Current...
  • Page 281 Instruction Manual PlantWeb Alerts D103412X012 July 2013 Table C‐2. Setting PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Related Parameters What the Alert is Detecting Guidelines for Setting (Group) (Default) (Default) (Default Alert Category) Double Acting Actuators— Enable the alert and configure it to report in the Failed Alert Category.
  • Page 282 Instruction Manual PlantWeb Alerts July 2013 D103412X012 Table C‐2. Setting PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Related Parameters What the Alert is Detecting Guidelines for Setting (Group) (Default) (Default) (Default Alert Category) Use default settings The temperature is greater Temperature High than the Temperature Hi Alert Alert Point ( 186_F)
  • Page 283 Instruction Manual PlantWeb Alerts D103412X012 July 2013 Table C‐2. Setting PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Related Parameters What the Alert is Detecting Guidelines for Setting (Group) (Default) (Default) (Default Alert Category) Packing Bonnets— enable the alert in the Maintenance Alert Category.
  • Page 284 Instruction Manual PlantWeb Alerts July 2013 D103412X012 Table C‐3. Using PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Recommended What the Alert is Detecting Effect on Valve/Instrument Help (Group) (Default) Action (Default Alert Category Processor Impaired Program Memory A pending Flash or NVM failure If configured for Self Test Replace PWB An error has been...
  • Page 285 Instruction Manual PlantWeb Alerts D103412X012 July 2013 Table C‐3. Using PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Recommended What the Alert is Detecting Effect on Valve/Instrument Help (Group) (Default) Action (Default Alert Category Travel Sensor Travel Sensor The travel feedback is within If configured for Self Test Check mounting Travel feedback value is...
  • Page 286 Instruction Manual PlantWeb Alerts July 2013 D103412X012 Table C‐3. Using PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Recommended What the Alert is Detecting Effect on Valve/Instrument Help (Group) (Default) Action (Default Alert Category Pressure Fallback Pressure Fallback A travel sensor failure or large None - Indicates a reduced Check instrument The instrument has...
  • Page 287 Instruction Manual PlantWeb Alerts D103412X012 July 2013 Table C‐3. Using PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Recommended What the Alert is Detecting Effect on Valve/Instrument Help (Group) (Default) Action (Default Alert Category Travel Deviation Travel Deviation The Travel Deviation has None - Indicates a reduced Check valve The valve travel is not...
  • Page 288 Instruction Manual PlantWeb Alerts July 2013 D103412X012 Table C‐3. Using PlantWeb Alerts (Continued) PlantWeb Alert Alert Condition Recommended What the Alert is Detecting Effect on Valve/Instrument Help (Group) (Default) Action (Default Alert Category Performance Critical Performance Critical performance issues None - Indicates control has Check I/P, Relay, On‐board diagnostics (Performance)
  • Page 289: Appendix D Foundation Fieldbus Communication

    Instruction Manual fieldbus Communication OUNDATION D103412X012 July 2013 Appendix D F fieldbus Communication9‐ OUNDATION D‐D‐ DVC6200f digital valve controllers use fieldbus to communicate with other fieldbus instruments and OUNDATION the control system. Fieldbus is an all digital, serial, two‐way communication system which interconnects “field” equipment such as transmitters, digital valve controllers, and process controllers.
  • Page 290: Instrument Specific Blocks

    Instruction Manual fieldbus Communication OUNDATION July 2013 D103412X012 Figure D‐1 illustrates the internal structure of a function block. When execution begins, input parameter values from other blocks are snapped‐in by the block. The input snap process ensures that these values do not change during the block execution.
  • Page 291: Block Modes

    Instruction Manual fieldbus Communication OUNDATION D103412X012 July 2013 Block Modes All blocks have modes. The mode determines the source of the set point, the destination of the output, how the block executes, and the relationship between setpoint and output. The block mode is determined by the Block Mode parameter.
  • Page 292: Explanation Of Modes

    Instruction Manual fieldbus Communication OUNDATION July 2013 D103412X012 Note A downstream block changing to Out of Service impacts the mode of the upstream block. Refer to the block hierarchy in figure D‐2. Figure D‐2. Digital Valve Controller Block Hierarchy Example RESOURCE BLOCK ANALOG OUTPUT TRANSDUCER...
  • Page 293: Examples Of Modes For Various Operation Statuses

    Instruction Manual fieldbus Communication OUNDATION D103412X012 July 2013 Remote Output (ROut)—The block outputs are set to the value of the remote output parameter that is written by a host computer or others. To prevent a sudden change in output, the block's calculations are initialized when a change in mode occurs.
  • Page 294: Status Propagation

    Instruction Manual fieldbus Communication OUNDATION July 2013 D103412X012 Table D‐3. Status Attribute Quality and Substatus Components Quality Substatus Good (NC) Non‐specific Good (NC) Active Block Alarm Good (NC) Active Advisory Alarm Good (NC) Active Critical Alarm Good (NC) Unack Block Alarm Good (NC) Unack Advisory Alarm Good (NC)
  • Page 295: Network Communication

    Instruction Manual fieldbus Communication OUNDATION D103412X012 July 2013 AO Block D If the valve position is below the low cutoff value, the AO block READBACK status limit is LOW_LIMITED. D If the valve position is above the high cutoff value, the AO block READBACK status limit is HIGH_LIMITED. D If the transducer block actual mode is Auto and the above conditions are not true, the AO block READBACK status limit is NOT_LIMITED.
  • Page 296: Device Communications

    Instruction Manual fieldbus Communication OUNDATION July 2013 D103412X012 D recognizes and adds new devices to the link. D removes non‐responsive devices from the link. D distributes Data Link (DL) and Link Scheduling (LS) time on the link. Data Link Time is a network‐wide time periodically distributed by the LAS to synchronize all device clocks on the bus.
  • Page 297: Unscheduled Transfers

    Instruction Manual fieldbus Communication OUNDATION D103412X012 July 2013 Figure D‐4. Scheduled Data Transfer Host System Schedule DT(A) CD (X, A) LAS=Link Active Scheduler P=Publisher Device X Device Y Device Z S=Subscriber CD=Compel Data DT=Data Transfer Packet B2713‐1 Unscheduled Transfers Figure D‐5 diagrams an unscheduled transfer. Unscheduled transfers are used for things like user‐initiated changes, including set point changes, mode changes, tuning changes, and upload/download.
  • Page 298: Function Block Scheduling

    Instruction Manual fieldbus Communication OUNDATION July 2013 D103412X012 D Report Distribution: This type of communication is used to broadcast and multicast event and trend reports. D Client/Server: This type of communication is used for request/ response exchanges between pairs of devices, such as a set point change.
  • Page 299: Appendix E Device Description Installation

    6‐digit hexadecimal equivalent of the manufacturer's identification number as defined by the Fieldbus Foundation. Fisher Controls' ID number is 5100 (or in the folder format 005100). This number is also stored in the instrument Resource Block in the parameter Mfg ID (parameter name MANUFAC_ID).
  • Page 300: Device Descriptions And Methods

    Instruction Manual Device Description Installation July 2013 D103412X012 D .ffo—This extension denotes a complete, tokenized, device description for the instrument as defined by the Fieldbus Foundation. D .cff—This extension denotes a capabilities file for the instrument as defined by the Fieldbus OUNDATION Common File Format specification.
  • Page 301 Be sure to select the correct DD for the DeltaV revision being used. The resource files are different for each revision of DeltaV. D Device descriptions furnished by Fisher contain only those files applicable to Fisher. All the files are located in the manufacturer ID Folder (005100 for xxxxxx in directory structure above).
  • Page 302: Installing Dds On Other Fieldbus Host Systems

    In general the following may apply: D Device descriptions furnished by Fisher contain only those files applicable to Fisher. All the files are located in the manufacturer ID Folder (005100 for xxxxxx in directory structure above). A readme file is included at the top level.
  • Page 303: Displaying The Device Description Revision

    Instruction Manual Device Description Installation D103412X012 July 2013 up the DD on your system. Note the folder where the decompressed files are placed. This information will be required later in the installation procedure. Note This procedure will install the necessary Device Description files (*.ffo and *.sym), and Capabilities file (*.cff) for the device. 1.
  • Page 304 Instruction Manual Device Description Installation July 2013 D103412X012...
  • Page 305: Appendix F Operating With A Deltav System

    Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Appendix F Operating with a DeltaV SystemF‐ F‐ Process Systems DeltaV System Getting Started with DeltaV Host Systems Appropriate Device Descriptions (DDs) installed. See the Device Description Compatibility table on page 298.
  • Page 306: Transducer Block Parameter - Configuration Index

    Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Table F‐1. Transducer Block (TB) Parameters - Configuration Index Parameter Label Path to Parameter Actual Travel Configure/Setup Detailed Setup Valve and Actuator Valve Actual Travel > > > > > Actuator Fail Action Configure/Setup Detailed Setup...
  • Page 307 Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Table F‐1. Transducer Block (TB) Parameters - Configuration Index (Continued) Parameter Label Path to Parameter Lever Style Configure/Setup Detailed Setup Valve and Actuator Actuator Lever Style > > > > >...
  • Page 308 Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Table F‐1. Transducer Block (TB) Parameters - Configuration Index (Continued) Parameter Label Path to Parameter Pressure A Device Variables Overview Pressures: Pressure A > > > Pressure A Sensor Failure Device Diagnostics Status Self Test Status: Pressure A Sensor Failure...
  • Page 309 Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Table F‐1. Transducer Block (TB) Parameters - Configuration Index (Continued) Parameter Label Path to Parameter Supply Pressure Sensor Alert Configure/Setup Detailed Setup Alerts Sensor Pressure Sensors: Supply Pressure Sensor Alert >...
  • Page 310 Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Table F‐1. Transducer Block (TB) Parameters - Configuration Index (Continued) Parameter Label Path to Parameter Travel Hi Alert Point Configure/Setup Detailed Setup Alerts Travel Travel Limit Hi/Lo Travel Hi Alert Point >...
  • Page 311 Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Table F‐2. Resource Block (RB) Parameters - Configuration Index Parameter Name Path to Parameter Alert Key Configure/Setup Setup Alarm Handling Alert Key > > > > Block Alarm: Alarm State Device Diagnostics Status Block Alarm: Alarm State...
  • Page 312: Introduction

    Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Introduction Note This appendix does not necessarily provide the latest information on the DeltaV system. For the latest information on using the DeltaV system, refer to the on‐line help or documentation supplied with the system. This appendix provides specific instructions for performing basic setup operations on the DeltaV host system.
  • Page 313 Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Figure F‐1. Navigating to AMS Device Manager DIGITAL VALVE CONTROLLER ICON AND NAME OPEN WITH AMS DEVICE MANAGER Figure F‐2. Accessing the Digital Valve Controller Through AMS Device Manager LEFT‐CLICK TO ACCESS THE DELTAV NETWORK DIGITAL VALVE...
  • Page 314: Methods

    Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Methods Transducer Block The following methods are accessed via the transducer block: Device Setup, Auto Travel Calibration, Manual Travel Calibration, Supply Sensor Calibration, Output A Sensor Calibration, Output B Sensor Calibration, Travel Sensor Adjust, Stroke Valve, Performance Tuner, Stabilize/Optimize, and Relay Adjust.
  • Page 315 Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Figure F‐3. Actions Menu ACTIONS CONFIGURE/SETUP RESOURCE BLOCK METHODS TRANSDUCER BLOCK METHODS Note To access diagnostic parameters left‐click on Device Diagnostics, and then on Digital Valve Controller (TRANSDUCER). See figure F‐4. To access device variables left‐click on Device Variables, and then on Digital Valve Controller (TRANSDUCER).
  • Page 316 Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Figure F‐4. Accessing Configure/Setup, Device Diagnostics, and Device Variables DIGITAL VALVE CONTROLLER (TRANSDUCER) RESOURCE (RESOURCE) DEVICE DIAGNOSTICS DEVICE VARIABLES Resource Block For detailed information on the parameters that are changed via the resource block, refer to the Detailed Setup section of this manual.
  • Page 317: Bringing The Device On-Line

    Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Bringing the Device On‐Line To completely configure the digital valve controller for use in a fieldbus loop, the following conditions must be met. Refer to DeltaV On‐Line‐Help or documentation for detailed information on accomplishing these steps. 1.
  • Page 318 Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Initial Device Setup When new FF devices are commissioned on the DeltaV system, device alarms are automatically enabled and default priorities are assigned to the alarms. Select properties on the device, then the Alarms and Displays tab, as shown in figure F‐5 to view whether device alarms are enabled on a particular device.
  • Page 319 Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Area Assignment Controllers use this area assignment to report node status (e.g. not communicating). Devices and control modules use this area assignment to determine where to send their alarms. Area A is the default area assignment for all controllers and workstations (see figures F‐6 and F‐7). Also, by default Area A is assigned to all workstations Alarms and Events subsystem.
  • Page 320 Instruction Manual Operating with a DeltaV System July 2013 D103412X012 because all workstations have Area A assigned. Consider lowering the priority of these alarms to ADVISORY until the end of the commissioning process. Reporting Alarms and Events to a Workstation Device alarm and event reporting is no different than control module reporting.
  • Page 321 Instruction Manual Operating with a DeltaV System D103412X012 July 2013 Figure F‐8. DeltaV Alarm Summary Configuration Each display alarm summary can be configured to match the alarm banner or be uniquely defined. Note If you think you should be seeing a device alarm in the alarm banner and it is not there, verify that the device is shown on the AlarmSum display.
  • Page 322 Instruction Manual Operating with a DeltaV System July 2013 D103412X012 Deciding Device Alarm Priorities Each device alarm, just like every process alarm, has a priority assigned to it. When a device is created, the device alarms are assigned default alarm priorities as shown in figure F‐9. Figure F‐9.
  • Page 323: Glossary

    Instruction Manual Glossary D103412X012 July 2013 Glossary Algorithm Deadband A set of logical steps to solve a problem or Region around a reference point that must be accomplish a task. A computer program contains exceeded before a new event occurs. one or more algorithms.
  • Page 324 A FIELDVUE instrument internal device that senses the output pressure from the pneumatic relay. Hardware Revision Revision number of the Fisher instrument Random Access Memory (RAM) hardware. The physical components of the A type of semiconductor memory that is normally instrument are defined as the hardware.
  • Page 325 Instruction Manual Glossary D103412X012 July 2013 Travel Sensor Motion Watch Dog Timer Increasing or decreasing air pressure causes the A timer that the microprocessor must pulse magnet assembly to move up or down or the periodically. If the microprocessor is unable to rotary shaft to turn clockwise or pulse the timer, the instrument shuts down.
  • Page 326 Instruction Manual Glossary July 2013 D103412X012...
  • Page 327: Index

    Instruction Manual Index D103412X012 July 2013 Index Alerts Configuration, 71 Electronics, 69 Environment, 73 Instrument, 69 Performance, 79 PlantWeb, 69 Acknowledge Option, Resource Block, 48 Proximity, 76 Sensor, 72 Act On IR, 131 Travel, 74 Action on Failure, DI Function Block, 205 AMS Device Manager, using, 310 Action on Fault Detection Analog Input (AI) Function Block, 5, 171...
  • Page 328 Instruction Manual Index July 2013 D103412X012 Auto Calibration, 214 Supply Pressure Sensor, 216 Calibration Date, 81 Calibration Location, 81 Calibration Person, 81 Classifications, Other Backup Link Master, 7 FSETAN, 8 GOST-R, 8 Basic Setup, 39 INMETRO, 8 Bench Set KGS, 8 Lower, 84 Natural Gas Certified, Single Seal device, 28 Upper, 84...
  • Page 329 Instruction Manual Index D103412X012 July 2013 Declaration of SEP, 9 Block Initialization, 202 Field Value Processing, 204 DeltaV ProfessionalPLUS Workstation, Installing DD I/O Selection, 202 on, 298 Modes, 202 DeltaV System parameters, 206 operating with, 303 Simulation, 205 Software Functionality/System Requirements, 310 Status Handling, 202 View Lists, 210 DeltaV Tune, for PID control loops, 132...
  • Page 330 Instruction Manual Index July 2013 D103412X012 Environment Alerts, 73, 225 Function Block Options, 46, 223 Supply Pressure, 73, 225 Function Block Scheduling, 296 Temperature Limit, 74, 225 Function Blocks, 5 Expert tuning, 43 Analog Input (AI), 5, 171 Pressure, 66 Analog Output (AO), 5, 113 Travel, 63 Discrete Input (DI), 201...
  • Page 331 Instruction Manual Index D103412X012 July 2013 Initialization and Back Calculation Requirements, OS Limit Propagation Function Block, 165 ISEL Function Block, 147 Transducer Block, 292 INMETRO, Brazil, Certification 8 Link Active Scheduler (LAS), 293 Input Characterization, 67 linkage‐less, non‐contacting position measurement, Device Variables, 230 Input Selection, ISEL Function Block, 150 Lower Bench Set, 84...
  • Page 332 Instruction Manual Index July 2013 D103412X012 Minimum Recorded Temperature Time, 228 Miscellaneous Options, 47, 223 natural gas, as supply medium, 7, 27, 28, 233 Mode Handling Natural Gas Certified, Single Seal device, 28 AO Function Block, 115 Other Classfications/Certifications, 8 DO Function Block, 191 NEPSI, China, Certification 8 PID Function Block, 128...
  • Page 333 Instruction Manual Index D103412X012 July 2013 Status Handling, 129 PlantWeb Alert Enable, 80 Parameters Advise Enable, 80 AI Function Block, 176 Failed Enable, 80 AO Function Block, 120 Maintenance Enable, 80 DI Function Block, 206 PlantWeb Alert Handling, Alert Handling, 86 DO Function Block, 195 PlantWeb Alert Reporting, 80 ISEL Function Block, 152...
  • Page 334 Instruction Manual Index July 2013 D103412X012 Pressure MLFB Gain, 66 Relay C, 215, 216 Relay Type, 81 Pressure Proportional Gain, 66 Remote Travel Sensor Connections, 34 Pressure Range Hi, 67 remote vent, 30 Pressure Range Lo, 67 Resource Block, 288 Pressure Sensors, Alerts, 72 Block Alarm, 221 Pressure Tuning, 65...
  • Page 335 Instruction Manual Index D103412X012 July 2013 Travel Sensor Alert, 72 Standby Firmware Revision, 49, 223 static discharge, avoiding, 233 Serial Number Actuator, 83 Status Handling Electronics, 48, 222 AI Function Block, 173 Factory, 48, 222 AO Function Block, 116 Field, 48, 222 DI Function Block, 202 Valve, 82 DO Function Block, 192...
  • Page 336 Instruction Manual Index July 2013 D103412X012 Transducer Block, 288 Travel Sensor, Alerts, 72 Block Error, 227 Travel Sensor Motion, 83, 84 Device Diagnostics, 224 Device Setup, 42 Device Variables, 229 Travel Target, Alert, 74 parameters, 87 Status and Limit Propagation, 291 Travel Tuning, 63 View Lists, 110 Travel Tuning Set, 63...
  • Page 337 Instruction Manual Index D103412X012 July 2013 Inlet Pressure, 82 MAI Function Block, 187 Manufacturer, 82 OS Function Block, 169 Model Number, 82 PID Function Block, 141 Outlet Pressure, 82 Resource Block, 61 Packing Type, 82 Transducer Block, 110 Serial Number, 82 Shaft Stem Diameter, 82 Size, 82 Style, 82...
  • Page 338 Instruction Manual Index July 2013 D103412X012...
  • Page 340 Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher, FIELDVUE, ValveLink, PlantWeb, DeltaV, and Baumann are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co.

Table of Contents