DVC6200 Digital Valve Controller

Detailed Setup (1-2)

Note
Detailed Setup is available for
instrument level HC, AD, PD, and ODV.
The Detailed Setup selection from the Configure /
Setup menu allows you to configure the digital valve
4
controller to your application. Table 4-1 lists the default
settings for a standard factory configuration. You can
adjust actuator response, set the various modes,
alerts, ranges, travel cutoffs and limits. You can also
restart the instrument and set the protection.

Mode and Protection (1-2-1)

Mode
D Instrument Mode
You can change the instrument mode by selecting
Mode and Protection, Instrument Mode from the
Detailed Setup menu, or press the Hot Key and select
Instrument Mode.
Instrument Mode allows you to either take the
instrument Out Of Service or place it In Service.
Taking the instrument Out Of Service allows you to
perform instrument calibration and also allows you to
change setup variables that affect control, provided
the calibration/configuration protection is properly set.
See Setting Protection.
Note
Some changes that require the
instrument to be taken Out Of Service
will not take effect until the instrument
is placed back In Service or the
instrument is restarted.
32
Table 4-1. Default Detailed Setup Parameters
Setup Parameter
Control Mode
Restart Control Mode
Zero Power Condition
Analog In Range Low
Analog In Range High
Analog Input Units
Feedback Connection
Travel Sensor Motion
Instrument
Configuration
Auxiliary Terminal Mode
Max Supply Pressure
Pressure Units
Temperature Units
Polling Address
Burst Mode Enable
Burst Command
Cmd #3 (Trending) Pressure
Tuning Set
Input Characteristic
Travel Limit High
Travel Limit Low
Travel/Pressure Cutoff High
Dynamic
Travel/Pressure Cutoff Low
Response and
Set Point Rate Open
Tuning
Set Point Rate Close
Set Point Filter Lag Time
Integrator Enable
Integral Gain
Integral Deadzone
Cycle Counter Alert Enable
Cycle Counter Alert Deadband
Cycle Counter Alert Point
Travel History
Alerts
Travel Accumulator Alert Enable
Travel Accumulator Deadband
Travel Accumulator Alert Point
Travel Deviation Alert Enable
Travel Deviation Alert Point
Travel Deviation Time
Pressure Deviation Alert
Enable
Deviation &
Pressure Deviation Alert Point
Other Alerts
Pressure Deviation Alert Time
Drive Signal Alert Enable
Supply Pressure Alert Enable
Supply Pressure Alert Point
Travel Alert Lo Enable
Lo Point
Travel Alert Hi Enable
Hi Point
Travel Alert Lo Lo Enable
Travel Alerts
Lo Lo Point
Travel Alert Hi Hi Enable
Hi Hi Point
Deadband
Shutdown Activated
Electronic
Power Starvation Alert Enable
Alerts
Non-Critical NVM Alert Enable
−continued on next page−
(1)
Default Setting
Analog
Resume Last
(2)
Valve Open
4 mA
20 mA
mA
Rotary − All
(2)
CW/To Bottom
(2)
Inst.
Disabled
(2)
20
(3)
PSI
(3)
F
0
No
3
A−B
(2)
F
Linear
125%
−25%
99.46%
0.50%
0%/sec
0%/sec
0 sec
Yes
9.4 repeats/minute
0.26%
No
1%
2147483647
No
1%
2147483647
Yes
5%
9.99 sec
Yes
(3)
5 psi
9.99 sec
Yes
Yes
(3)
19 psi
No
−25%
No
125%
No
−25%
No
125%
5%
Yes
No
No
September 2010