Wiring Practices; Control System Requirements; Hart Filter - Fisher FIELDVUE DVC6200 Instruction Manual

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200:
Table of Contents

Advertisement

Installation
May 2013
CAUTION
Failure to secure the cable wires in the support clips in step 9 can result in broken wires in applications with high levels of
vibration.
9. Secure the cable wires, using the support clips in the DVC6215 feedback unit (as shown in figure 2‐26), to help
prevent shifting and movement of the wires.
10. Replace and hand‐tighten all covers.
Figure 2‐26. Secure Wires in Clips

Wiring Practices

Control System Requirements

There are several parameters that should be checked to ensure the control system is compatible with the DVC6200
digital valve controller.

HART Filter

Depending on the control system you are using, a HART filter may be needed to allow HART communication. The
HART filter is a passive device that is inserted in field wiring from the HART loop. The filter is normally installed near the
field wiring terminals of the control system I/O (see figure 2‐27). Its purpose is to effectively isolate the control system
output from modulated HART communication signals and raise the impedance of the control system to allow HART
communication. For more information on the description and use of the HART filter, refer to the appropriate HART
filter instruction manual.
To determine if your system requires a filter contact your Emerson Process Management sales office.
Note
A HART filter is typically NOT required for any of the Emerson Process Management control systems, including PROVOXt, RS3t,
and DeltaVt systems.
34
CLIP TO SUPPORT THE WIRES OF
THE 4-CONDUCTOR SHIELDED CABLE
CLIP TO SUPPORT THE
INSULATED SHIELD WIRE
Instruction Manual
D103409X012

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents