Use these instructions to mount a FIELDVUE™
DVC6200/DVC2000 to a Linear Actuator.
WARNING
Avoid personal injury or property
damage from sudden release of process
pressure or bursting of parts. Before
performing any maintenance
operations:
 Always wear protective clothing,
gloves, and eyewear.
 Do not remove the actuator from
the valve while the valve is still
pressurized.
 Disconnect any operating lines
providing air pressure, electric power, or
a control signal to the actuator. Be sure
the actuator cannot suddenly open or
close the valve.
 Use bypass valves or completely
shut off the process to isolate the valve
from process pressure. Relieve process
pressure from both sides of the valve.
 Vent the pneumatic actuator
loading pressure and relieve any
actuator spring precompression.
 Use lock-out procedures to be sure
that the above measures stay in effect
while you work on the equipment.
 Check with your process or safety
engineer for any additional measures
that must be taken to protect against
process media.
The visual aids in this document are for general
reference representation only. Refer to the
appropriate actuator instruction manual for actuator
installation, operation, maintenance, and parts
identification as this manual may or may not include
all components shown for kit installation.
1
1.
Isolate the control valve from the process line
pressure and release pressure from both sides of the
valve body. Shut off all pressure lines to the actuator,
releasing all pressure from the actuator. Use lock-out
procedures to be sure that the above measures stay in
effect while you work on the equipment.
2.
Attach connector arm assembly to stem block
using provided fasteners (including spacers and stud
bolts, if applicable).
DVC6200/DVC2000
Digital Valve Controller on
Linear Actuator

Advertisement

loading

Summary of Contents for Fisher FIELDVUE DVC6200

  • Page 1 Mounting Instructions DVC6200/DVC2000 D103996X012 Digital Valve Controller on May 2014 Linear Actuator Isolate the control valve from the process line Use these instructions to mount a FIELDVUE™ pressure and release pressure from both sides of the DVC6200/DVC2000 to a Linear Actuator. valve body.
  • Page 2 Mounting Instructions DVC6200/DVC2000 D103996X012 Digital Valve Controller on May 2014 Linear Actuator For fork-style connector arms remove the nuts and Loosely attach array to extension arm using indicator disk from the stem. Place the fork-style provided fasteners. (Array not included with kit) extension arm flush with the bottom of the stem block onto the stem.
  • Page 3 Mounting Instructions DVC6200/DVC2000 D103996X012 Digital Valve Controller on May 2014 Linear Actuator Attach extension arm with array assembly to Attach mounting plate to actuator using provided connector arm. hardware (including stud bolts, spacers, and L-brackets, if applicable).
  • Page 4 Mounting Instructions DVC6200/DVC2000 D103996X012 Digital Valve Controller on May 2014 Linear Actuator Attach aligning template to mounting plate. Adjust height of array until the middle line of the aligning template is level with the corresponding line of the array relative to stem block position. ***Care needs to be taken to ensure that line the index marks on the array do not move outside of the center index mark on the alignment template***...
  • Page 5 Mounting Instructions DVC6200/DVC2000 D103996X012 Digital Valve Controller on May 2014 Linear Actuator Attach insert assembly into the magnet housing Remove aligning template. Attach device to slot on the back of the device using the provided 3m mounting bracket using provided fasteners. adhesive strip.
  • Page 6 Mounting Instructions DVC6200/DVC2000 D103996X012 Digital Valve Controller on May 2014 Linear Actuator Attach remote mount air filter regulator (if Final Assembly applicable).
  • Page 7 Mounting Instructions DVC6200/DVC2000 D103996X012 Digital Valve Controller on May 2014 Linear Actuator Air Filter Regulator DVC6200 Shield Alignment Template Extension Arm Spacer Connector Arm Insert Assembly U-Bracket Common Mounting Bracket Linear Feedback Array DVC2000 Mounting Plate...
  • Page 8 Responsibility for the selection, use and maintenance of any product remains with the purchaser and end user. Fisherand FIELDVUE are marks owned by Fisher Controls International LLC, a member of the Emerson Process Management business unit of Emerson Electric Co.

This manual is also suitable for:

Fieldvue dvc2000