Instruction Manual
D103409X012
Table 4‐10. Estimates for Partial Stroke Pressure Limits
Actuator Style
Relay Type
A or C
Spring and
Diaphragm
B
A or C
Single Acting Piston
B
Double Acting Piston
A
Zero Power Condition
PST Starting Point
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Partial Stroke Pressure Limit
Open
Pmin - 0.25 * (Bench Set High - Bench Set Low)
Closed
Pmax + 0.25 * (Bench Set High - Bench Set Low)
Open
Pmax + 0.25 * (Bench Set High - Bench Set Low)
Closed
Pmin - 0.25 * (Bench Set High - Bench Set Low)
Open
Pmax + 0.25 * (Bench Set High - Bench Set Low)
Closed
Pmin - 0.25 * (Bench Set High - Bench Set Low)
Open
Pmin - 0.25 * (Bench Set High - Bench Set Low)
Closed
Pmax + 0.25 * (Bench Set High - Bench Set Low)
Open
0.5 * Pmin
Closed
Pmax + 0.5 * (Psupply - Pmax)
Open
Pmax + 0.5 * (Psupply - Pmax)
Closed
0.5 * Pmin
Open
Pmax + 0.5 * (Psupply - Pmax)
Closed
0.5 * Pmin
Open
0.5 * Pmin
Closed
Pmax + 0.5 * (Psupply - Pmax)
Open
Pmin - 0.5 * (Psupply + Pmin)
Closed
Pmax + 0.5 * (Psupply - Pmax)
Open
Pmax + 0.5 * (Psupply - Pmax)
Closed
Pmin - 0.5 * (Psupply + Pmin)
Detailed Setup
May 2013
(1)
75