Fisher FIELDVUE DVC6200 Instruction Manual page 23

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200:
Table of Contents

Advertisement

Instruction Manual
D103409X012
Figure 2‐15. Air‐to‐Open Fisher GX Magnet Assembly
Alignment
RETAINING
SLOT
INDEX MARK
W9218
5. Tighten the fasteners and remove the alignment template. Continue on with the appropriate step 6 below.
Air‐to‐Open GX Actuators
6. The pneumatic output port on the DVC6215 lines up with the integral GX actuator pneumatic port. See figure 2‐17.
7. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad on the side that has the open
pneumatic port. Be sure to place the O‐ring between the feedback units pneumatic output and the actuator
mounting pad. Pneumatic tubing between the feedback unit and the actuator is not required because the air
passages are internal to the actuator.
8. Connect the pneumatic tubing from the DVC6205 to the feedback units pneumatic port provided on the front of
the DVC6215 as shown in figure 2‐17.
Figure 2‐17. Modifications for Fisher GX Actuator; Air‐to‐Open Construction Only
PNEUMATIC PORT
INSTALL O‐RING
X0128
ALIGNMENT TEMPLATE
PNEUMATIC TUBING
FROM THE DVC6205
Figure 2‐16. Air‐to‐Close Fisher GX Magnet Assembly
Alignment
ALIGNMENT TEMPLATE
RETAINING
SLOT
INDEX MARK
W9219
Installation
May 2013