Heating system inspection and maintenance
7.4.1
Checking the operating pressure (sealed
systems)
On sealed heating systems the pressure gauge needle
must be within the green field.
Ensure that the red pressure gauge needle is set to the
required operating pressure.
Create an operating pressure (overpressure)
of at least 1 bar.
z Check the heating system operating pressure.
The operating pressure is too low if the pressure gauge
needle indicates below the green field. The system needs
to be topped up with water.
z Top up with water until the desired operating pressure
is reached.
z Vent the heating system during filling.