Page 1
Propane Conversion kit Condensing gas boiler instructions Required Input Rates Logamax plus GB162-80 kW Logamx plus GB162-100 kW 270,000 btu/hr 315,000 btu/hr This kit and instructions are for converting the GB162 model boilers from Natural Gas to Liquid Propane. WARNING! This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer‘s instructions and all...
Checking and adjusting the gas/air ratio Carrying out a tightness test in operating conditions Measuring the CO content Lighting Instructions Operating Instructions Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Indicates presence of hazards due to electric shock. Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
• Torx key Tx25 1 × • Torx key Tx30 1 × • Torx screw 3 × • Screw M5x12 thread 4 × Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Loosen both retaining clips on the burner cover fig. 3, [1]) and pull the plugs ( fig. 3, [2]) from the fig. 6). gas valve. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 6
80 kW/ (0-1,220) 100 kW LPG P 0-4,000 4.70(0.193) 73983 (0-1,220) Tab. 1 Gas orifice diameter 6720615033-014.1TD Fig. 10 Installing the gas flange Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Fill out the required information on the conversion label. B Close the boiler door and lock the fastener by turning the vent key through ¼ rotation in a clockwise direction. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Enter the value measured in the start-up report. B Open the gas shut-off valve again. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Check all gaskets and joints in the burner gas circuit for leaks while the burner is operational, using a leak detection agent. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Connect the boiler to the power supply. B Switch on the boiler using the main switch ( fig. 18). Reset 6720615033-022.1TD Fig. 18 Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!