Buderus Logano GE615 Installation And Maintenance Instructions Manual page 33

Calorific value forced draft sectional boiler
Hide thumbs Also See for Logano GE615:
Table of Contents

Advertisement

z Place lower lengthways bars from the side onto the
cross bars with the folded edges facing inwards and
the slotted hole towards the rear, and screw in place
with self-tapping screws.
z Push rear section insulation onto the flue outlet. The
cut-out for the boiler return must point upwards.
z Hook the rear section insulation onto the top rear bar
with two tension springs.
z Close the slit below the flue outlet with tension springs.
z Push rectangular insulation onto the top front bar.
z Fasten insulation with 3 tension springs.
z Feed burner cable over the insulation, down the side of
the boiler block.
To prevent damage to the burner cable while
opening the burner door, the burner cable
must always be fed down the hinge side –
whichever side the burner door may be hung
on.
Logano GE615 - We reserve the right to make any changes due to technical modifications.
Fig 42 Fitting lower lengthways bars and insulation
1
Top rear bar
2
Rear section insulation
3
Tension springs
4
Lower lengthways bar
5
Lower lengthways bar
Fig 43 Fitting the rectangular insulation and burner
cable
1
Insulation
2
Tension springs
3
Burner cable
4
Installation
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents