Type
Display
1)
code
Fault code Cause
V
EE
626
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 - Technical specifications are subject to change without prior notice
Description
Electrode voltage
Voltage to ioniza-
incorrect.
tion electrode too
low.
Troubleshooting
Testing
sequence/Cause
Action
Check connecting
Replace defective
lead between SAFe
lead or rectify
and electrode for
breaks.
breaks or damage.
Check electrode
Align burner rod/
gaps and electrode
electrode Replace
for damage.
defective electrode.
Check power supply
Ensure power sup-
voltage at MC10
ply voltage is cor-
input (at least
rect.
102 V).
Check if voltage
Eliminate voltage
dips are occurring
dips.
(e.g. when large
electrical consum-
ers are switched on)
If all checks OK,
replace SAFe.
10