Page 1
Gas-fired condensing boiler Installation and maintenance instructions for contractors Logano plus GB402 Read carefully prior to installation and maintenance.
7.8.3 Accessing the service level on the RC35 and 2.7.1 Logano plus GB402 dimensions ....8 displaying monitoring data ..... . 27 2.7.2 Specifications .
Page 3
Keyword index ........61 Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Any other combinations, accessories and wearing parts may only be used if these are specifically designed for the application and impair neither the performance characteristics nor the safety requirements. Logano plus GB402 – 6 720 820 700 (2018/01)
CE-0085BU0332 Table 2 Approval data Determined use The Logano plus GB402 is designed for conventional use as a gas condensing boiler for DHW and central heating. Only gas supplied by the public gas supplier can be used. Observe the details on the data plate and the specification (...
Information on the device Product Description The Logano plus GB402 is a gas condensing boiler with an aluminium heat exchanger. Fig. 1 Logano plus GB402 - main components Boiler front panel The main components of the Logano plus GB402 ( Fig. 1) are: Gas valve •...
* available separately Scope of delivery The Logano plus GB402 is supplied as standard with a Logamatic BC10 ACCESSORIES basic controller and the MC10 control unit in 3 separate packages. Many individual accessories are available for this boiler.
+0,3 Ø 250 +0,7 6 720 618 585-16.4T Fig. 3 Dimensions and connections for the Logano plus GB402 (dimensions in mm) Flue outlet MAG Optional connection for a diaphragm expansion vessel to protect AKO Condensate outlet a single boiler Combustion air pipe inlet (balanced flue operation only,...
EN 1443 Corrosion resistance classification to be used Min. 2 Min. 2 Min. 2 Min. 2 Min. 2 for flue system in accordance with EN 1443 Table 4 Specifications Logano plus GB402 – 6 720 820 700 (2018/01)
6 (country-specific gas category and supply pressures) is adhered to. Product data for energy consumption The product data on energy consumption can be found in the operating instructions for the user. Logano plus GB402 – 6 720 820 700 (2018/01)
NOTICE: System damage through frost! ▶ If there is the risk that pipework may freeze up when operating in room temperature-dependent mode (e.g. radiator in a garage), set the pump overrun time to 24 hours. Logano plus GB402 – 6 720 820 700 (2018/01)
Validity of regulations Modified regulations or supplements are also valid at the time of installation and must be observed. 1) In addition to this, country-specific and local regulations must be observed. Logano plus GB402 – 6 720 820 700 (2018/01)
Protect boiler from contamination if the boiler is not to be taken into use immediately. Dispose of packaging in an environmentally responsible manner. Fig. 5 Separating the boiler from the pallet Locking screws Fixing bar Logano plus GB402 – 6 720 820 700 (2018/01)
Where applicable, allow extra wall clearances for additional components, for example DHW cylinder, pipe connections or other components on the flue gas side etc. Fig. 8 Levelling the boiler Fig. 7 Wall clearances in the installation room Logano plus GB402 – 6 720 820 700 (2018/01)
The boiler must not be connected to any combined flue system with motorised combustion systems (e.g. combined heat and power unit). Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Connect the condensate hose from the siphon with a slope to the neutralising system. Where the neutralising system is installed outside the boiler, there is the option of guiding the condensate hose through the aperture in the back panel. Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Seal in distributor [2] at flow connector [1] using a suitable sealant. ▶ Remove the union at the cap valve fitting [3]. ▶ Fit union with gasket to connector of fitting manifold [4] and secure to the cap valve on the distributor. Logano plus GB402 – 6 720 820 700 (2018/01)
Make the connection of a DHW cylinder to the flow and return on site. The MC10 + BC10 control unit can switch the required external cylinder primary pump ( MC10/BC10 instructions). Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Prior to filling the heating system, carefully read the enclosed operator's log on water quality. ▶ Open safety caps on all automatic air vent valves. ▶ Open the fill and drain valve. Logano plus GB402 – 6 720 820 700 (2018/01)
NOTICE: System damage through incorrect control! ▶ Route high and low voltage cables separately inside the cable conduits. ▶ Route all cables that run towards the back through the cable trunking. Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Press the front of the module downwards. stress. ▶ Secure the gas line with pipe clips so that the gas connection is free from any stresses. ▶ Close gas isolation valve. Fig. 23 Inserting the function module Logano plus GB402 – 6 720 820 700 (2018/01)
• Applicable for 10.9 to 12.4 kWh/m Upper Wobbe index for 0 °C, 1013 mbar: • Set to 12.2 kWh/m • Applicable for 11.5 to 13.1 kWh/m Table 11 Factory settings Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Press the key until the decimal point in the status display illuminates (at least 2 seconds). ▶ Carry out the flue gas test. Logano plus GB402 – 6 720 820 700 (2018/01)
The values monitored are displayed as a list; in other words, more venting values will appear if the rotary selector is turned. The current burner output (set/actual) and the flame current can be checked in these menus. Logano plus GB402 – 6 720 820 700 (2018/01)
Page 28
▶ Read off load at the RC35 or via the service key. values (natural gas DK CO rat.=12.0 Vol. – %) from Chapter 12.5, ▶ Wait until 20 % of the load is reached. page 60 Logano plus GB402 – 6 720 820 700 (2018/01)
Page 29
▶ Press to change to the next status display. incorrect appliance setup, burner and/or heat exchanger contamination The boiler temperature is displayed. or burner faults. ▶ Identify and eliminate the cause. Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Explain to the customer what to do in an emergency, e.g. a fire, ▶ To prevent corrosion, carefully wipe off the leak referring to the operating instructions. detection agent afterwards. ▶ Hand over the technical documents to the user. Logano plus GB402 – 6 720 820 700 (2018/01)
Function tests – Checking the ionisation current ____________ μA Installing casing parts Inform operator; hand over technical documentation Correct commissioning by the installing contractor Signature:______________________ User signature Signature:______________________ Table 13 Commissioning report Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Slightly lift the front panel and remove by pulling forwards. DANGER: Risk to life through explosion of flammable gasses! ▶ Only registered gas fitters are permitted to carry out work on gas lines (observe local regulations). Logano plus GB402 – 6 720 820 700 (2018/01)
15 x 1 18 x 1 22 x 1 28 x 1.5 35 x 1.5 45 x 1.5 Table 16 Pipework volume (V ) subject to pipe length and diameter pipe Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Check all joints in the tested pipework section using a foaming leak detection agent. ▶ If required, seal any leaks and repeat the test. ▶ If no leaks are found, replace gas train. Logano plus GB402 – 6 720 820 700 (2018/01)
Fig. 43 Removing the siphon ▶ Observe all regulations and standards applicable in Condensate pan outlet your country regarding the prevention of drinking Siphon water contamination. ▶ In Europe, observe standard EN 1717. Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Carefully pull out the burner towards you. 6 720 618 585-37.2T Fig. 45 Undoing the gas connection Fig. 47 Undoing the nuts at the mixture manifold Screws Fixing nuts Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Re-install the burner rod with a new gasket. CAUTION: Risk of injury from sharp edges of cleaning blade! ▶ To avoid injury, wear protective gloves when cleaning the boiler using cleaning blades (accessories). Logano plus GB402 – 6 720 820 700 (2018/01)
Page 38
▶ Re-install the siphon ( Chapter 6.2, page 17). ▶ Check the condensate hose between the boiler flue connection and the siphon for free flow. 6720646293-01.1BU Fig. 53 View of cleaning cover; 320 kW 395-620 kW Logano plus GB402 – 6 720 820 700 (2018/01)
▶ For completing maintenance see Chapter 10.9, page 41. Gas valve If spare parts replacement is necessary, see from Chapter 10.8. ▶ For completing maintenance see Chapter 10.9, page 41. Logano plus GB402 – 6 720 820 700 (2018/01)
▶ Remove mounting plate [1] from the fan. ▶ Undo both rear screws [3] (joint between carriage [2] and fan [5] (do not remove). ▶ Support the fan and remove both front screws [4]. Logano plus GB402 – 6 720 820 700 (2018/01)
[1] as shown in Fig. 63 (below the guide rod). Fig. 62 Replacing the fan/carriage gaskets Fig. 63 Plug-in connection at the electrode block ▶ After the fan installation, check the gasket for correct seating. Logano plus GB402 – 6 720 820 700 (2018/01)
14. Check that the control unit is set correctly to meet – demand (see documents for the control unit). 15. Final checking of inspection work. – Confirm correct inspection Company stamp / date / signature Table 18 Logano plus GB402 – 6 720 820 700 (2018/01)
Page 45
Carry out a function check. Confirm professional maintenance. Company stamp/signature Table 20 Date: ______ Date: ______ Date: ______ Date: ______ Date: ______ Company stamp/signature Company stamp/signature Company stamp/signature Company stamp/signature Company stamp/signature Table 21 Logano plus GB402 – 6 720 820 700 (2018/01)
Should the fault reoccur, repeat the reset two or three times. 6 720 801 303-02.1T Fig. 65 Clearing a fault on the burner control unit Reset button Fig. 64 Clearing a fault with the "Reset" key Logano plus GB402 – 6 720 820 700 (2018/01)
> 15K. temperature sensor using a boiler sensor (high limit thermometer. safety cut-out (STB)) and Check whether a cast section is compare with the curve. blocked with dirt. Table 22 Operating codes Logano plus GB402 – 6 720 820 700 (2018/01)
Unfavourable hydraulics in two-boiler systems: the boilers influence each other reciprocally, e.g. via the return or flow. Table 23 Fault displays 1) V = locking; B = blocking Logano plus GB402 – 6 720 820 700 (2018/01)
Page 49
(Does the flame extinguish cut-out responds. reached its maximum after a controlled shutdown?) permitted level. Table 23 Fault displays 1) V = locking; B = blocking Logano plus GB402 – 6 720 820 700 (2018/01)
Page 50
Replace ionisation electrode. 0.9 μA. the electrodes. Replace gas train. Check gas train function. Table 23 Fault displays 1) V = locking; B = blocking Logano plus GB402 – 6 720 820 700 (2018/01)
Page 51
If required, replace faulty has opened. external components, components. components. which are integrated in the MC10 safety chain has been interrupted. Table 23 Fault displays 1) V = locking; B = blocking Logano plus GB402 – 6 720 820 700 (2018/01)
Page 52
Remedy any short circuit. sensor fault short circuit (voltage < sensor. (short circuit). 0.5 V). Check water pressure sensor. Replace water pressure sensor. Table 23 Fault displays 1) V = locking; B = blocking Logano plus GB402 – 6 720 820 700 (2018/01)
Page 53
Please note: this fault can only be reset via The SAFe has developed a fault. Replace the SAFe. the button on the SAFe. Table 23 Fault displays 1) V = locking; B = blocking Logano plus GB402 – 6 720 820 700 (2018/01)
Page 54
Table 23 Fault displays 1) V = locking; B = blocking Logano plus GB402 – 6 720 820 700 (2018/01)
........................off The burner control unit is not in operation Table 24 Display of the operating condition of the burner via the lighting of the reset button. Permanently GREEN Logano plus GB402 – 6 720 820 700 (2018/01)
NOTICE: Operating faults through power failure! ▶ When connecting external components to the MC10 control unit, ensure that these components do not exceed a total maximum power consumption of 5 A. Logano plus GB402 – 6 720 820 700 (2018/01)
Page 57
Appendix Fig. 67 MC10 connection diagram 1) The total current of all externally connected components must not exceed 5 A. Logano plus GB402 – 6 720 820 700 (2018/01)
Page 58
Logamatic MC10 Function modules xM10 Spare fuse 10 AT RC35 programming unit or dummy cover BC10 basic controller Appliance fuse 10 AT Fuse inside the MC10 Fuse inside the BC10 basic controller Logano plus GB402 – 6 720 820 700 (2018/01)