Buderus Logano plus GB312 Installation Manual page 85

Table of Contents

Advertisement

Type
Display
1)
code
Fault code Cause
V
CY
573
V
CY
574
V
LP
570
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 - Technical specifications are subject to change without prior notice
Description
Flow temperature
Control unit is
receiving implausi-
< 23 °F (< -5 °C) (cir-
ble signals from
cuit break)
flow temperature
sensor.
Flow temperature
Control unit is
receiving implausi-
>266°F (>130°C)
ble signals from
(short circuit)
flow temperature
sensor.
Too many resets via
Too many resets
the interface.
have been received
via the interface
within a certain
period.
Important: this fault
can only be reset
by the button on
the SAFe.
Troubleshooting
Testing
sequence/Cause
Action
Check connecting
Replace connect-
lead between SAFe
ing lead if neces-
and return sensor.
sary
Check electrical
Rectify any contact
connection of con-
problems
necting lead to
Replace tempera-
SAFe.
ture sensor if nec-
Check resistance
essary
levels of tempera-
If temperature sen-
ture sensor against
sor resistances are
table
correct but volt-
Check voltage at
ages incorrect,
temperature sensor
replace SAFe
terminals on SAFe
against table
Check connecting
Replace connect-
lead between SAFe
ing lead if neces-
and return sensor.
sary
Check electrical
Rectify any contact
connection of con-
problems
necting lead to
Replace tempera-
SAFe.
ture sensor if nec-
Check resistance
essary
levels of tempera-
If temperature sen-
ture sensor against
sor resistances are
table
correct but volt-
Check voltage at
ages incorrect,
temperature sensor
replace SAFe
terminals on SAFe
against table
Faults have continu-
Identify and elimi-
ally been simply
nate the cause of
reset and not recti-
the problem caus-
fied.
ing the resets.
There is a fault on
Replace BC10.
the BC10 causing
Replace SAFe.
continual resets.
There is a malfunc-
tion on the SAFe.
10
85