Type
Display
1)
code
Fault code Cause
V
6L
561
B
7A
550
B
7A
551
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 - Technical specifications are subject to change without prior notice
Description
5 power-up
The burner control
sequences (power
unit has switched
supply disconnection
off 5 times during
during burner start-
the burner start-up
up).
sequence.
Voltage too low.
The power supply
voltage is too low.
Power failure.
There has been a
brief loss of power.
Troubleshooting
Testing
sequence/Cause
Action
(continued from
previous page)
SAFe burner con-
Replace SAFe.
trol unit defective.
Ignition transformer
Replace ignition
defective (delayed
transformer.
or non-existent
spark, "violent" start-
tup).
Check the 120V
Reset burner con-
power supply to the
trol unit.
control unit.
Rectify power sup-
ply problem.
The power supply
Ensure adequate
voltage must not
power supply volt-
drop below 102V.
age.
Check power supply
Rectify any contact
lead for loose con-
problems.
tacts.
Check wiring and
proper contact of
power plug on
MC10/SAFe.
10
81