Caution: Risk of system damage due to in-
adequate condensate drainage.
V The condensate that forms in the flue pipe
must be drained away from the boiler via
the condensate drain on the condensate
pan.
Caution: Disruption of operation due to high
wind.
If no T-piece or 90° elbow is fitted on the end
of flue pipe, high winds may cause the boiler
to shut down.
V Always make sure that there is a T-piece
or a 90° elbow fitted depending on the de-
sign of the flue system.
V Use only a T-piece or 90° elbow (Catego-
ry IV) made by the selected flue system
manufacturer.
With regard to possible restrictions and in-
spections for flue systems, consult the local
building and fire safety authorities. Observe
the national regulations.
In the Commonwealth of Massachusetts the
requirements about carbon monoxide detec-
tors must be followed.
In the case of flue systems sealed with high
temperature silicon from a cartridge, the sili-
con must be allowed to dry for 24 hours be-
fore commissioning the boiler.
Danger: Risk of fatal injury due to poisoning
by escaping flue gas.
V After carrying out any of the installations
referred to, check that all connections
throughout the entire flue system are
properly joined and sealed.
V Check seams and joints for leaks.
V Have the entire flue system checked once
a year by a qualified heating contractor.