Gas valve replacement Condensing gas boiler instructions Required Input Rates Logamax plus GB162-80 kW Logamx plus GB162-100 kW 290,000 btu/hr 333,000 btu/hr This instruction is for replacing the gas valve for the GB162 model boilers with Natural Gas. WARNING! Replacement of a gas valve must be done by a qualified service agency in accordance with the manufacturer‘s instructions and all...
Checking and adjusting the gas/air ratio Carrying out a tightness test in operating conditions Measuring the carbon monoxide content (CO) Lighting Instructions Operating Instructions Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Indicates presence of hazards due to electric shock. Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
• these instructions • O-ring (fan-venturi) • O-ring (gas train) • sealing (gas pipe) • Torx keys Tx25 and Tx30 • Torx screws (flange). Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Pull the air suction tube from the fan ( fig. 5). 6720615033-003.1TD Fig. 2 Opening the boiler door 6720615033-006.1TD Fig. 5 Pulling the air suction tube from the fan Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 6
8.40 73983 80 kW/ (0 - 1,220) (0.331) 100 kW Tab. 1 Gas orifice diameter 6720615033-014.1TD Fig. 10 Installing the gas flange Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Open the gas shut-off valve again. B Enter the value measured in the start-up report. 1) Measured statically perpendicular to flow at full load. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Do not spray the leak testing agent onto cables, plugs or electrical connection lines. Do not allow it to drip onto them either. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
B Connect the heating system to the power supply. B Switch on the heating system using the main switch fig. 18). Reset 6720615033-022.1TD Fig. 18 Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!