10
Troubleshooting
Type
Display
1)
code
Fault code Cause
V
4U
521
V
4U
522
V
4Y
523
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
76
Description
Temperature differ-
Temperature differ-
ence at twin boiler
ence between flow
sensor too great.
temperature sen-
sors 1 and 2 too
great (divergence
of > 9 °F/2s; 5 K/
2s).
Short circuit between
A fault has been
boiler sensors 1 and
detected in temper-
2.
ature sensor test
mode.
Circuit break on flow
Temperature at flow
temperature sensor.
temperature sen-
sor.
< 23 °F (< -5 °C)
Logano plus GB312 - Technical specifications are subject to change without prior notice
Testing
sequence/Cause
Action
Check connectors
Clean contacts/
on boiler sensor and
replace connecting
SAFe for dirt/dam-
lead if necessary.
age.
If there are discrep-
Check boiler sensor
ancies in the sensor
resistance against
readings or the
sensor characteris-
connector is defec-
tic/visually check
tive, the tempera-
temperature sensor.
ture sensor must be
replaced.
Check boiler sensor
voltage levels
Replace SAFe if
against table (SAFe
there are discrep-
documentation).
ancies.
Check sensor lead.
Replace if dam-
aged.
Check connector.
If dirty, clean or
Check sensor read-
replace as neces-
ings against sensor
sary.
characteristic.
If connector is
Check temperature
loose, reconnect
sensor voltage levels
properly.
against table (SAFe
documentation).
Replace tempera-
ture sensor if there
are discrepancies.
Replace SAFe if
there are discrep-
ancies.
Check sensor lead.
Replace if dam-
aged.
Check connector.
If dirty, clean or
Check sensor read-
replace as neces-
ings against sensor
sary.
characteristic.
If connector is
Check temperature
loose, reconnect
sensor voltage levels
properly.
against table (SAFe
documentation).
Replace tempera-
ture sensor if there
are discrepancies.
Replace SAFe if
there are discrep-
ancies.