Buderus Logano plus GB312 Installation Manual page 74

Table of Contents

Advertisement

10
Troubleshooting
Type
Display
Event
1)
code
code
BC
OE
-
BC
OU
-
BC
OC
-
BC
OL
-
BC
OF
-
Tab. 16 Operating codes1) V = locking; B = inhibiting; BC = operating code
74
Cause
Description
The appliance is
The current heat
in standby mode,
demand from the
heat demand is
system is lower than
present but too
that supplied by the
much heat is
minimum burner
being delivered.
modulation setting.
Beginning of
-
sequence for
starting up
burner.
Beginning of
-
burner start-up.
Gas valve open-
-
ing.
Lack of flow
Temperature differ-
through boiler.
ence between supply
and return > 27 °F,
> 15 K.
Temperature differ-
ence between supply
and high limit tem-
perature sensor
> 27 °F, 15 K.
Logano plus GB312 - Technical specifications are subject to change without prior notice
Testing sequence/
Cause
Action
-
-
-
-
-
-
-
-
Check supply temp.
Adjust setting of
with BC10,
boiler pump.
Check return temp.
with RC35 or S-Key,
Check resistance of
Check surface temp.
high limit sensor.
of cast section with
mounted high limit
sensor with temp.
meter.
Check if cast section
is blocked with dirt.