Buderus Logano plus GB312 Installation Manual page 84

Table of Contents

Advertisement

10
Troubleshooting
Type
Display
1)
code
Fault code Cause
V
CY
566
V
CY
567
V
CO
568
V
CO
569
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
84
Description
Return temperature
Control unit is
receiving implausi-
< 23 °F (< -5 °C) (cir-
ble signals from
cuit break)
return sensor.
Return temperature
Control unit is
receiving implausi-
> 266 °F (> 130 °C)
ble signals from
(short circuit)
return sensor.
Water pressure sen-
Water pressure
sor fault (break in
sensor circuit break
cable).
(voltage > 3.5 V)
Water pressure sen-
Water pressure
sor fault (short circuit).
sensor short circuit
(voltage < 0.5 V).
Logano plus GB312 - Technical specifications are subject to change without prior notice
Testing
sequence/Cause
Action
Check connecting
Replace connect-
lead between SAFe
ing lead if neces-
and return sensor.
sary.
Check electrical
Rectify any contact
connection of con-
problems.
necting lead to
Replace tempera-
SAFe.
ture sensor if nec-
Check resistance
essary.
levels of tempera-
If temperature sen-
ture sensor against
sor resistances are
table.
correct but volt-
Check voltage at
ages incorrect,
temperature sensor
replace SAFe.
terminals on SAFe
against table.
Check connecting
Replace connect-
lead between SAFe
ing lead if neces-
and return sensor.
sary.
Check electrical
Rectify any contact
connection of con-
problems.
necting lead to
Replace tempera-
SAFe.
ture sensor if nec-
Check resistance
essary.
levels of tempera-
If temperature sen-
ture sensor against
sor resistances are
table.
correct but volt-
Check voltage at
ages incorrect,
temperature sensor
replace SAFe.
terminals on SAFe
against table.
Check connection
Establish good
between SAFe and
electrical contact.
water pressure sen-
Replace lead if nec-
sor for poor con-
essary.
tact, breaks and
damage.
Check water pres-
Replace water
sure sensor.
pressure sensor.
Check connecting
Rectify any short
lead to water pres-
circuits.
sure sensor.
Replace water
Check water pres-
pressure sensor.
sure sensor.

Advertisement