Buderus Logano plus GB312 Installation Manual page 83

Table of Contents

Advertisement

Type
Display
1)
code
Fault code Cause
V
8Y
590
V
8Y
591
V
9Y
500
501
502
503
Tab. 17 Fault messages
1) V = locking; B = inhibiting; BC = operating code
Logano plus GB312 - Technical specifications are subject to change without prior notice
Description
Pressure switch in
Break in pressure
safety assembly has
switch safety
tripped.
assembly during
burner operation.
Error checking safety
SAFe pressure
assembly.
switch has not
tripped.
Internal SAFe relay
Internal electronic
fault.
fault on SAFe.
Troubleshooting
Testing
sequence/Cause
Action
Check whether low
Measure the gas
gas pressure switch
pressure at 100%
(available sepa-
boiler modulation.
rately) is breaking
Check low gas
circuit during opera-
pressure switch
tion.
(available sepa-
rately) setting.
Check if the air sup-
Check flue/air sup-
ply switch or flue
ply pipe for block-
gas pressure switch
ages.
opens while the
boiler is operating.
Check whether
Replace gas valve
SAFe or high gas
pressure switch
(available sepa-
rately) is breaking
circuit during opera-
tion
Section 10.3, page
87 ff
Check whether gas
Ensure gas supply
supply pressure is
pressure is
> 3 inches w.c.
> 3 inches w.c.
Check setting of
Adjust setting of
SAFe pressure
SAFe pressure
switch.
switch to 3 inches
w.c.
Check connector on
Insert connector
gas valve is properly
properly.
seated.
Replace SAFe
pressure switch
and wiring.
Replace SAFe.
Press Reset button
If fault recurs after
and wait to see if
reset, SAFe must
fault is eliminated.
be replaced.
10
83

Advertisement

Table of Contents
loading

Table of Contents