Framing Specifications
1. Cold climate installation recommendation: When installing this fire-
place against non insulated exterior wall or chase, it is recom -
mended that the outer walls be insulated to conform to applicable
insulation codes. Drywall must be installed over insulation to prevent
contact of insulation and unit.
2. Choose fireplace location and frame in accordance with the fireplace
framing dimensions specified (See Framing Diagrams). Bend nailing
tabs forward on left and right of unit and place fireplace into framed
enclosure. This allows for 1/2" in front of framing tabs for finishing
materials.
3. Drywall or other material can extend flush with the appliance on the
bottom, sides and top of fireplace. (louvered models only)
For Propane Horizontal Installations the venting must be a minimum of one foot vertical off the flue before the elbow on any
horizontal runs of one foot or greater. This allows for cleaner combustion and greatly reduces carboning and cleaning of glass.
HBZDV47 Louvered

Framing for your Gas Fireplace

TOP VIEW
11"
21
8
" DIA.
3 2
4. When installing horizontal with a 90 degree bend maintain a mini-
mum of two and a half (2.5") inches above the bend in enclo-
sures,insulation sleeve is required. If greater than six and a half (6.5")
an insulation sleeve is not required.
5. For HBZDV with louvers combustible floor can raise 1" above the bot-
tom of the fireplace. For HBZDV with CVCK (Clean view Circulating
Kit) floor or hearth can raise 7" above the bottom of the fireplace
with portions being combustible and non combustible. See drawing
Below.
6. When installing MQHB47SWCC wall surround, the fireplace must be
raised a minimum of 3 1/2" above the finished floor, to accommodate
the wall surround. When installing MQHB47SWCV wall surround the
fireplace must be raised 2 3/4" above the finished floor. The fireplace
may be raised higher but the 60" clearance measured from the bot-
tom of the fireplace to the ceiling must be maintained at all times. (i.e.
For an 8 ft. ceiling the unit can be raised only 36 inches.)
HBZDV47 WITH CVCK (CLEAN VIEW CIRCULATING KIT)
11"
9