Checking Gas Connections - Procom FBD32RT Owner's Operation And Installation Manual

Vent-free gas
Hide thumbs Also See for FBD32RT:
Table of Contents

Advertisement

WARNING: Test all gas piping
and connections for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply
a noncorrosive leak detection
fluid to all joints. If bubbles form,
there is a leak. Correct all leaks
at once.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect heater with its appliance main
gas valve (control valve) and equipment
shutoff valve from gas supply piping sys-
tem. Pressures in excess of 1/2 PSIG will
damage heater regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping sys-
tem. Apply noncorrosive leak detection
fluid to all joints. If bubbles form, there
may be a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
fittings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 15).
Equipment
Shutoff Valve
Figure 15 - Equipment Shutoff Valve
16
INSTALLATION

CHECKING GAS CONNECTIONS

Open
Closed
www.usaprocom.com
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter to equip-
ment shutoff valve for natural gas or
propane/LP supply to equipment shutoff
valve for propane/LP (see Figure 16 or
17). Apply a noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Fig-
ure 15).
2. Open main gas valve located on or near
gas meter for natural gas or open pro-
pane/LP supply tank valve.
3. Make sure control knob of heater is in the
OFF position.
Propane/LP
Equipment
Supply Tank
Shutoff Valve
External Regulator with
Vent Pointing Down
Figure 16 - Checking Gas Joints for
Propane/LP Gas
Gas Meter
Equipment Shutoff Valve
Figure 17 - Checking Gas Joints for
Natural Gas
Control Valve
Location
Control Valve
Location
200069-01A