7. OUTLINE OF CONTROL CIRCUIT
OUTLINE OF SPECIFICATION
Duplicate Release
1st
ON
TC release
(ON@54
o
C)
o
(OFF@52
C)
Fan speed
(16 waves)
Fan OFF
A subsequent release signal ON reduces the fan speed by
one wave/minute and continues to do so while release
signal stays ON. (Min.speed=fan off)
When release signal OFF is transmitted then after 1
minute fan speed will be increased by one wave every
˚
minute, until Te>5
C.
Reset operation
When Reset operation:
When the fan speed returns to maximum and the Te
˚
temp is <5
C then the operation goes back to normal,
and the fan speed is held constant.
96
www.heronhill.co.uk
2nd
OFF
ON
OFF
o
Te >5
C
1min
1min
Te >5
1min
1min
If Te <5
o
C then fan speed + 1wave/minute
If Te >5
o
C then fan speed held