Toshiba RAV-104SBH-PE Service Manual page 66

Split type, heat pump built-in duct type ceiling type wall type carcase type low wall/painted floor type 2 way cassette type 4 way cassette type
Table of Contents

Advertisement

4.33
RAV-264AH8-PE
No
PARTS NAME
1
Compressor
2
Outdoor Unit fan motor
Running capacitor for
3
outdoor fan motor
Magnetic contactor
4
(Supplier: Fuji Electric)
5
High pressure switch
6
Solenoid coil for four-way valve
7
Crankcase heater
Sensor for defrosting
8
Fuse
9
Sensor for cooling operation in low
10
ambient temperature
11
Solenoid coil for two-way valve
12
Reverse Phase Protector
13
Transformer (Outdoor Unit)
14
Bimetal thermostat
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
4. SPECIFICATIONS OF ELECTRICAL PARTS
TYPE
YG460X3F-MS
SMF-230-63N-2
FMCa-1
ACB-2TB04W
CHV-AC240V
NEV AC 240V
FT-67
CS-12A
www.heronhill.co.uk
SPECIFICATIONS
Output (rated) 2.2kW, 2 pole, 380/415V, 3 Phase, 50Hz
Winding Resistance: Common Run 4.28Ω
Output (rated) 63W, 6 pole, 230V, 1 Phase, 50Hz
Winding Resistance: Common Run (Blk-Red) 79.4Ω
Common Start (Blk-White) 106Ω
AC 400V, 4µF
AC 380-440V, 50Hz
2
Tripping pressure 30kgf/cm
G
Resetting pressure 23kgf/cm
AC 220-240V
AC 240V, 28W
Maximum input
15.5mA
T5A
Maximum input
15.5mA
AC 220-240V, 50Hz
380/415V, 3 Phase, 50Hz
AC 187-264V
˚
Tripping temperature: 110
C
˚
Resetting temperature: 90
C
66
at 20
at 25
at 25
2
G
˚
C
-12
kΩ
67.5
21.3
˚
C
-12
kΩ
67.5
21.3
Fax: 01823 665807
˚
C
˚
C
˚
C
10
10

Hide quick links: