Piping Length/Additional Refrigerant Volume
12.7
The amount of refrigerant put into the Outdoor Unit at the factory is sufficient to fill up to 20m of
!
refrigerant pipework.
If the length of the refrigerant pipework is 20m or less, addition of refrigerant at the installation site
!
is unnecessary.
If the length of the pipework exceeds 20m, extra refrigerant must be added. Refer to the table
!
below for details of the extra amounts.
Overcharge or undercharge of refrigerant in the Outdoor Unit will cause malfunction of
!
the compressor.
The prescribed amount of the replenishment of the refrigerant is shown in the table below:
MODEL
Less
than
(RAV-)
20m
134AH-PE
164AH-PE
264AH/AH8-PE
364AH8-PE
364AH8-1-PE
464AH8-PE
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
12. PERFORMANCE CHARACTERISTICS
Additional amount of refrigerant to add at
±
installation site (kg)
50g
Less
Less
Less
Less
than
than
than
than
25m
30m
35m
40m
0.18
0.35
0.18
0.35
0.18
0.35
0.18
0.35
0.53
0.7
0.18
0.35
0.53
0.7
0.25
0.5
0.75
1.0
!
ADD ONLY R407C REFRIGERANT TO THESE UNITS
www.heronhill.co.uk
Recharge amount if unit is reclaimed
Less
Less
Less
Less
Less
than
than
than
than
than
45m
50m
5m
20m
25m
0.79
1.05
1.23
0.94
1.2
1.38
1.64
1.9
2.08
0.88
1.05
2.44
2.7
2.88
0.88
1.05
2.34
2.6
2.78 2.95
1.25
1.5
3.13
3.5
3.75
104
±
(kg)
50g
Less
Less
Less
Less
Less
than
than
than
than
than
30m
35m
40m
45m
50m
1.4
1.55
2.25
3.05
3.23
3.4
3.58
3.75
3.13
3.3
3.48
3.65
4.0
4.25
4.5
4.75
5.0