Piping Length/Additional Refrigerant Volume
12.7
The amount of refrigerant put into the Outdoor Unit at the factory is sufficient to fill up to 20m of
!
refrigerant pipework.
If the length of the refrigerant pipework is 20m or less, addition of refrigerant at the installation site
!
is unnecessary.
If the length of the pipework exceeds 20m, extra refrigerant must be added. Refer to the table
!
below for details of the extra amounts.
Overcharge or undercharge of refrigerant in the Outdoor Unit will cause malfunction of
!
the compressor.
The prescribed amount of the replenishment of the refrigerant is shown in the table below:
MODEL
Less
than
(RAV-)
20m
134AH-PE
164AH-PE
264AH/AH8-PE
364AH8-PE
364AH8-1-PE
464AH8-PE
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
12. PERFORMANCE CHARACTERISTICS
Additional amount of refrigerant to add at
±
installation site (kg)
50g
Less
Less
Less
Less
than
than
than
than
25m
30m
35m
40m
0.18
0.35
—
—
0.18
0.35
—
—
0.18
0.35
—
—
0.18
0.35
0.53
0.7
0.18
0.35
0.53
0.7
0.25
0.5
0.75
1.0
!
ADD ONLY R407C REFRIGERANT TO THESE UNITS
www.heronhill.co.uk
Recharge amount if unit is reclaimed
Less
Less
Less
Less
Less
than
than
than
than
than
45m
50m
5m
20m
25m
—
—
0.79
1.05
1.23
—
—
0.94
1.2
1.38
—
—
1.64
1.9
2.08
0.88
1.05
2.44
2.7
2.88
0.88
1.05
2.34
2.6
2.78 2.95
1.25
1.5
3.13
3.5
3.75
104
±
(kg)
50g
Less
Less
Less
Less
Less
than
than
than
than
than
30m
35m
40m
45m
50m
1.4
—
—
—
—
1.55
—
—
—
—
2.25
—
—
—
—
3.05
3.23
3.4
3.58
3.75
3.13
3.3
3.48
3.65
4.0
4.25
4.5
4.75
5.0
Fax: 01823 665807